Page 114: 58 trx ac drives, Wiring recommendations

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

©

2000–2003 Schneider Electric All Rights Reserved

114

09/2003

Table 3: Recommended Fuses: 400/460 V Three-Phase Drive Controllers

F1-F2-F3

F1-F2-F3

Motor

Drive Controller

CT, VTLN

Line Power Fuses

Drive Controller

VTLN

Line Power Fuses

hp

kW

ATV58H•••••

Class J

[1]

ATV58H•••••

Class J

[1]

1

0.75

U18N4

5

2

1.5

U29N4

10

3

2.2

U41N4

12

3

U54N4

15

5

4

U72N4

20

U54N4X

20

7.5

5.5

U90N4

25

U72N4X

25

10

7.5

D12N4

40

U90N4X

40

15

11

D16N4

50

D12N4X

50

20

15

D23N4

70

D16N4X

70

25

18.5

D23N4X

70

hp

kW

CTLN

ATV58H•••••

F1-F2-F3

Class J

[2]

CT, VTLN

ATV58H•••••

F1-F2-F3

Class J

[2]

VT

ATV58H•••••

F1-F2-F3

Class J

[2]

20

11

D28N4

70

25

18.5

D33N4

80

D28N4

70

D28N4

70

30

22

D46N4

100

D33N4

80

D28N4

90

40

30

D54N4

125

D46N4

100

D33N4

110

50

37

D64N4

150

D54N4

125

D46N4

150

60

45

D79N4

200

D64N4

150

D54N4

175

75

55

D79N4

175

D64N4

200

100

75

D79N4

200

hp

kW

VT

ATV58H•••••

F1-F2-F3

[3]

125

90

C10N4X

FWH-300A

150

110

C13N4X

FWH-400A

200

132

C15N4X

FWH-500A

250

160

C19N4X

FWH-600A

300

200

C23N4X

FWH-700A

350

220

C25N4X

FWH-800A

400

250

C28N4X

FWH-900A

450

280

C31N4X

FWH-900A

500

315

C33N4X

FWH-1000A

[1] Fast-acting or time
delay Class J fuses are
acceptable. Class T
fuses are acceptable.
Class CC fuses may be
used if recommended
fuse rating is 30 A or
lower.

[2] Fast-acting Class J
fuses. Class T fuses are
acceptable.

[3] Use the Bussmann
part numbers provided
or equivalent.

CT

Constant Torque

CTLN

Constant Torque Low
Noise

VTLN

Variable Torque Low
Noise

VT

Variable Torque