External RFI Input Filters

NOTE: Line reactors and filters are intended for separate mounting and wiring by the user. Ratings are
based on NEC (NFPA 70) 430-150 current ratings. If the drive has a higher FLA rating, use the “A” rating
to select the appropriate filter.

Supply Voltage

ATV58 Models

Maximum Length of
Shielded Cable

[1]

Nominal
Current (In)
of the Filter

Weight

Catalog
Number

EN 55011
Class A

EN 55022
Class B

Single-Phase
200 to 240 Vac
50/60 Hz

ATV58•U09M2, ATV58•U18M2

50 m/164 ft

20 m/65 ft

10 A

1.7 kg/3.7 lb

VW3A58401

ATV58•U29M2, ATV58•U41M2

50 m/164 ft

20 m/65 ft

25 A

3.6 kg/7.9 lb

VW3A58402

ATV58•U72M2

50 m/164 ft

20 m/65 ft

25 A

5.0 kg/11.0 lb

VW3A58403

ATV58•U90M2, ATV58•D12M2

50 m/164 ft

20 m/65 ft

40 A

10.0 kg/22.0 lb

VW3A58404

3-Phase
200 to 240 Vac
50/60 Hz

ATV58•U29M2, ATV58•U41M2

50 m/164 ft

20 m/65 ft

25 A

3.6 kg/7.9 lb

VW3A58402

ATV58•U54M2, ATV58•U72M2

50 m/164 ft

20 m/65 ft

25 A

5.0 kg/11.0 lb

VW3A58403

ATV58•U90M2, ATV58•D12M2

50 m/164 ft

20 m/65 ft

45 A

10.0 kg/22.0 lb

VW3A58404

3-Phase
208 to 240 Vac
50/60 Hz

ATV58HD16M2X, ATV58HD23M2X

n/a

n/a

80 A

13.0 kg/28.6 lb

VW3A58407

ATV58HD28M2X, ATV58HD33M2X,
ATV58HD46M2X

n/a

n/a

160 A

20.0 kg/44.0 lb

VW3A58408

3-Phase
400 to 460 Vac
50/60 Hz

ATV58•U18N4, ATV58•U29N4,
ATV58•U41N4

50 m/164 ft

20 m/65 ft

25 A

3.6 kg/7.9 lb

VW3A58402

ATV58•U54N4, ATV58•U72N4,
ATV58•U90N4

50 m/164 ft

20 m/65 ft

25 A

5.0 kg/11.0 lb

VW3A58403

ATV58•D12N4, ATV58•D16N4

50 m/164 ft

20 m/65 ft

45 A

10.0 kg/22.0 lb

VW3A58404

ATV58•D23N4

50 m/164 ft

20 m/65 ft

45 A

13.0 kg/28.6 lb

VW3A58405

ATV58HD28N4

200 m/656 ft

100 m/328 ft

50 A

13.0 kg/28.6 lb

VW3A58406

ATV58HD33N4, ATV58HD46N4

200 m/656 ft

100 m/328 ft

80 A

13.0 kg/28.6 lb

VW3A58407

ATV58HD54N4, ATV58HD64N4,
ATV58HD79N4

200 m/656 ft

100 m/328 ft

160 A

20.0 kg/44.0 lb

VW3A58408

[1] The filter selection tables give the maximum length for the shielded cables which connect the motors to the drive controllers for a switching frequency

of 0.5 to 12 kHz. These limits are given for information only as they depend on the interference capacity of the motors and the cables used. For motors
connected in parallel, the total of the lengths must be taken into account.

Line Reactors—480 V Rated Three Phase

460 V Drive Rating

Open Style
Part Number

Enclosed
Part Number

Approx.
Wt.
(lbs.)

Enclosure
Dimensions
HxWxD
(in.)

HP

kW

1

. . .

RL00202

RL00212

11

8x8x6

2–3

. . .

RL00403

RL00413

12

8x8x6

5

. . .

RL00803

RL00813

18

15x13x13

7.5

. . .

RL01203

RL01213

25

15x13x13

10

. . .

RL01803

RL01813

49

15x13x13

15

. . .

RL02503

RL02513

49

15x13x13

20–25

. . .

RL03503

RL03513

61

15x13x13

30

. . .

RL04503

RL04513

70

15x13x13

40

. . .

RL05503

RL05513

72

15x13x13

50–60

. . .

RL08003

RL08013

86

15x13x13

75

. . .

RL10003

RL10013

105

15x13x13

100

. . .

RL13003

RL13013

105

15x13x13

125

. . .

RL16003

RL16013

105

15x13x13

150

. . .

RL20003

RL20013

131

15x13x13

200

. . .

RL25003

RL25013

185

24x17x17

250

. . .

RL32003

RL32013

235

24x17x17

300

. . .

RL40003

RL40013

245

24x17x17

350–400

. . .

RL50003

RL50013

335

24x17x17

450–500

. . .

RL60003

RL60013

335

24x17x17

Line Reactors

Line Reactors.tif

Advertising