Class 8839 58M Enclosed AC Drives

Factory Engineered Modifications

155

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

The standard enclosure dimensions of the Class 8839 58M Enclosed drives may not apply to orders
containing E-Mods. Orders containing E-Mods may carry a UL508A label in lieu of a UL508C label.

CONTROL OPTIONS

Form modifications in the E200 series cover control circuit engineered features for the Class 8839 58M
Enclosed drive controller.

Rules: Requires selection of 24 V power supply option Z10.

Rules: Limited to one meter selection unless Analog input option card (H09) is selected. If H09 is selected, one additional meter can
be selected.

Rules: Available only if one additional N.O. Drive Run Contact standard option K10 is selected.

Rules: Available only if one additional N.O. Aux. Bypass Run Contact standard option M10 is selected.

Rules: Available only if one additional N.O. Drive Fault Contact standard option L10 is selected.

Rules: Available only if one N.O. Auto Mode Contact standard option O10 is selected.

Rules: Available on all configurations.

Rules: Available on all configurations.

Mod
E200

Menu-based message display center

Large full text screen display and setup of drive parameters. Provides meter display functions, I/O map, and fault
message display
Note: The message display center replaces the standard keypad display.

Mod Door-mounted

meters

E201

Analog percent speed meter scaled 0 to 120% base speed

E202

Analog percent current scaled 0 to 100% of rated output current

E203

Digital ammeter (amperes) scaled 0 to 2 times rated output amperes

E204

Digital speed meter (frequency) scaled 0 to 72 Hz output frequency

E205

Digital percent speed meter scaled 0 to 120% base speed

E206

Digital percent current scaled 0 to 100% of rated output current

Mod
E211

Door-mounted Modbus/PDA port

Provides one 9-pin D shell port for connection to a PDA or a PC with PowerSuite software. A two-position selector
switch is used to select between PDA port operation and keypad operation.

Mod
E212

Auxiliary drive run contacts

Provides three additional Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One Form 'C' contact for drive run is supplied as standard.

Mod
E213

Auxiliary bypass run contacts

Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One N.O. contact for bypass run is supplied as standard when bypass is provided.

Mod
E214

Auxiliary drive fail contacts

Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One Form 'C' contact for drive fault indication is supplied as standard.

Mod
E215

Auxiliary auto mode contacts

Provides three Form 'C' contacts rated 5 A @ 120 Vac wired to terminal blocks for customer use.
Note: One N.O. contact for auto mode indication is supplied as standard when auto mode operation is provided.

Mod
E216

Adjustable restart delay timer

Provides an adjustable On Time Delay Relay for power up restart function, mounted and wired for AFC mode (hand or
auto) mode and/or in the bypass mode (hand/auto).

Mod
E217

Motor space heater

Provides control circuit contacts, 120 V, 150–500 VA supply and fusing wired to terminals for customer use.
Note: Specify VA requirements at time of order entry in the 'Engineering Notes' field within Q2C.