Line reactors, Three phase line reactors – Schneider Electric ALTIVAR 58 TRX User Manual

Page 160

Advertising
background image

Class 8839 58M Enclosed AC Drives

Three Phase Line Reactors

160

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

The Class 8839 58M Enclosed AC Drives are
designed to operate from industrial power systems
with normal AC line conditions without the need of
additional line impedance from either an isolation
transformer or a line reactor. However, when
abnormal line conditions exist, additional line
impedance may be required. Typically, line reactors
are used to:

• Reduce the input rms current to the AC drive

ratings

• Lower the available fault current on high fault

distribution systems

• Limit the total harmonic voltage distortion from

the AC drive at the point of common coupling to
align with IEEE 519 guidelines

• Prevent AC drive nuisance tripping due to

transient overvoltages from power factor
correction capacitor switching

Line Reactors:

1. The line reactors are manufactured by

MTE, Inc.

2. Harmonic compensated up to 150% of

nominal current ratings

3. 5% nominal reactance

4. Refer to the following publications on the

subject of harmonics and benefits of drive
isolation transformers:

8803PD9402–Power Systems Harmonics–

Cause and Effects of AC Drives.

7460HO9501–Drive Isolation

Transformers-Application, Selection and
Specification Data

7460PD9501– Drive Isolation

Transformers–Solutions to Power Quality

HP Rating

208/230 VAC Line Reactor
Part No. (Integrated)

460 VAC Line Reactor
Part No. (Integrated)

Enclosed Standard Option

1

RL–01202

RL–00802

A10

2

RL–01202

RL–00802

A10

3

RL–01202

RL–00802

A10

5

RL–01801

RL–01203

A10

7.5

RL–01801

RL–01203

A10

10

RL–03501

RL–01802

A10

15

RL–03501

RL–01802

A10

20

RL–08001

RL–01802

A10

25

RL–08001

RL–03502

A10

30

RL–10001

RL–03502

A10

40

RL–10001

RL–03502

A10

50

RL–16002

RL–08002

A10

60

RL–08002

A10

75

RL–10002

A10

100

RL–13002

A10

125

RL–16013

A10

150

RL–20013

A10

200

RL–25013

A10

250

RL–32013

A10

300

RL–40013

A10

350

RL–50013

A10

400

RL–50013

A10

450

RL-60013

A10

500

RL-60013

A10

Load

Line

A1

B1

C1

A2

B2

C2

Li

n

eLo

ad

.e

p

s

Advertising