Class 8839 58M Enclosed AC Drives

Three Phase Drive Isolation Transformers

162

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Drive Isolation transformers are designed for maximum benefit when applied to an AC drive.
In addition to the functional comparison of a line reactor, drive isolation transformers are normally used
for one of the following reasons over a standard line reactor:

1. Match system voltage to drive rating.

2. Meet local or plant codes that require isolation.

3. Capable of correcting line voltage unbalance conditions commonly seen with open delta and corner

grounded delta distribution systems.

4. Provides continuity of service for nuisance grounding.

5. Reduces drive induced currents in supply feeder ground and limit ground fault currents.

6. Isolate the electrical common mode noise generated in solid state controllers from the distribution

system.

The Class 8839 58M Enclosed AC drives have a high fault withstand capability (up to 65,000 A or
100,000 A depending upon configuration). For these reasons, Square D does not require the use of a
drive isolation transformer for isolation purposes unless the system requires one or more of the six
functions listed above.

Notes:

To complete catalog number: Select the voltage required from chart. Insert the voltage code number in
place of the ( ) in the catalog number

Three Phase 60 Hz Class B (IEEE 597-1983)

HP Rating

kVA

Catalog Number

1–5

7.5

7T( )HDIT

7.5

11

11T( )HDIT

10

15

15T( )HDIT

15

20

20T( )HDIT

20

27

27T( )HDIT

25

34

34T( )HDIT

30

40

40T( )HDIT

40

51

51T( )HDIT

50

63

63T( )HDIT

60

75

75T( )HDIT

75

93

93T( )HDIT

100

118

118T( )HDIT

125

145

145T( )HDIT

150

175

175T( )HDIT

200

220

220T( )HDIT

250

275

275T( )HDIT

300

330

330T( )HDIT

400

440

440T( )HDIT

450

550

550T( )HDIT

500

550

550T( )HDIT

Voltage Codes

Code

Primary

Secondary

142

230 Delta

230Y/132

143

230 Delta

460Y/265

144

460 Delta

230Y/132

145

460 Delta

460Y/265

146

575 Delta

230Y/132

147

575 Delta

460Y/265