Enclosed adjustable frequency drives (1 to 500 hp), Part 1 general, 01 scope of work – Schneider Electric ALTIVAR 58 TRX User Manual

Page 175: 02 references, 03 submittals

Advertising
background image

Class 8839 58M Enclosed AC Drives

Specifications

175

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

ENCLOSED ADJUSTABLE FREQUENCY
DRIVES (1 TO 500 HP)

Note to Specifier: These specifications apply to
Enclosed Adjustable Frequency Drive Controllers,
herein referred to as AC Drives. The power
converter is a component of the AC Drive. To
ensure project compatibility, these specifications
follow the Construction Specifications Institute
(CSI) format. Copies of this specification are
available from the Square D

®

website,

www.squared.com. Application information
directly affects the type and rating of AC Drive that
will be quoted. [Brackets] are provided where
such data and options should be included or
considered depending on application
requirements. Please contact your local Square D
distributor or sales representative for specification
assistance regarding a particular application. The
AC Drive specification should be included in
Division 16 (Electrical) for proper coordination
with the electrical distribution sy
stem.

PART 1 GENERAL

1.01 SCOPE OF WORK

a. This section provides specification

requirements for adjustable frequency drives,
variable speed drives or herein identified as
AC Drives for use with NEMA

®

B design AC

motors.

b. The AC Drive manufacturer shall furnish, field

test, adjust and certify all installed AC Drives
for satisfactory operation.

c. Any exceptions/deviations to this specification

shall be indicated in writing to the specifying
engineer and submitted with the quotation.

1.02 REFERENCES

a. NFPA-70 (2002) “National Electric Code

(NEC

®

)”

b. ANSI C84.1 (R2002) “Electric Power Systems

and Equipment - Voltage Ratings (60Hz)”

c. CSA

®

C22.2 No.14-95 (R2001) “Industrial

Control Equipment”

d. UL508A (2003) “Standard for Safety for

Industrial Control Panels”

e. UL508C (2002) “Standard for Safety for Power

Conversion Equipment”

f.

NFPA 79 (2002) “Electrical Equipment of
Industrial Machines/Industrial Machinery

g. NEMA ICS7 (2000) “Industrial Control and

Systems: Adjustable Speed Drives

h. NEMA ICS7.1 (2000) “Safety Standards for

Construction and Guide for Selection,
Installation, and Operation of Adjustable
Speed Drive Systems

i.

NEMA 250 (1997) “Enclosures for Electrical
Equipment (1000V maximum

j.

IEC 61800-2 (1998-03) “Adjustable speed
electrical power drive systems - Part 2:
General requirements - rating specifications
for low voltage adjustable frequency AC power
drive systems”

k. IEC 61800-3 (1998-06) “Adjustable speed

electrical power drive systems - Part 3: EMC
product standard including specific test
methods”

l.

IEC 61800-5-1 (2003-02) “Adjustable speed
electrical power drive systems - Part 5-1:
Safety requirements - Electrical, thermal and
energy

m. IEC 61800-6 (2003-03) “Adjustable speed

electrical power drive systems - Part 6: Guide
for determination of types of load duty and
corresponding current ratings.”

n. EGSA 101P (1995a) “Engine Driven

Generator Sets - Performance Standard”

o. IEEE 519 (1992) “Recommended Practices

and Requirements for Harmonic Control in
Electrical Power Systems”

1.03 SUBMITTALS

a. [6] copies of approval drawings shall be

furnished for Engineer’s approval prior to
factory assembly of the AC Drives. These
drawings shall consist of elementary power
and control wiring diagrams and enclosure
outline drawings. The enclosure drawings
shall include front and side views of the
enclosures with overall dimensions and
weights shown, conduit entrance locations
and nameplate legend details.

b. Standard catalog sheets showing voltage,

horsepower, maximum current ratings and
recommended replacement parts with part
numbers shall be furnished for each different
horsepower rated AC Drive provided.

Advertising
This manual is related to the following products: