Standard features, Power circuit descriptions, Test-normal selector switch description – Schneider Electric ALTIVAR 58 TRX User Manual

Page 187: Fire/freezestat interlock description, Class 8839 econoflex™ ac drives

Advertising
background image

Class 8839 Econoflex™ AC Drives

Standard Features

187

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

STANDARD FEATURES

The Econoflex controller includes:

• Circuit breaker disconnect with lockout capability.

• Insulated Gate Bipolar Transistor (IGBT) power converter with PWM output waveform.

• Door-mounted keypad.

• Form C AFC fault contact, rated 2 A at 120 Vac, wired to customer terminal block.

• Form C AFC run contact, rated 2 A at 120 Vac, wired to customer terminal block.

• Fire/Freezestat interlock location provided to customer terminal block.

• Factory enclosed line reactor (25 to 100 HP at 460 Vac, 15 to 50 HP at 208/230 Vac).

• Top and bottom conduit knockouts for Type 1 and Type 12K.

• Industrial rated control operators.

• UL 508C listed with NEMA ICS 7.1 compliance.

• Instruction bulletin 30072-450-10.

When Bypass is selected the Econoflex controller also includes:

• Isolation and Bypass Contactors, mechanically and electrically interlocked.

• AFC-OFF-BYPASS Selector Switch.

• TEST-NORMAL Selector Switch.

• Class 20 overload protection.

Power Circuit Descriptions

• Power Circuit W operates the motor from the power converter.

• Power Circuit Y operates the motor from the power converter or from full voltage line power, bypass.

The isolation and bypass contactors are mechanically and electrically interlocked. The two contactor
isolation/bypass configurations sequence the contactors to provide the isolation of the motor when it
is not running.

Test-Normal Selector Switch Description

The Test-Normal selector switch is mounted on the door of the controller and supplied with the bypass
circuit. The Test-Normal switch is used to test the power converter while operating the motor in bypass.
To use this function and maintain motor operation, place the following switches in these positions:

• AFC-Off-Bypass: Set the switch to Bypass to run the motor at full speed across the line.

• Test-Normal: Set the switch to Test.

• Hand-Off-Auto: Set the switch to Hand. Use the manual speed potentiometer to change the speed

reference and observe power converter operation.

Fire/Freezestat Interlock Description

User terminals are supplied for accepting a user supplied fire/freezestat interlock (normally closed).
When the user supplied contact is opened the drive output isolation contactor and bypass contactor
open and the motor stops.