Class 8839 Econoflex™ AC Drives

Factory Modifications

190

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

FACTORY MODIFICATIONS (CONTINUED)

Miscellaneous Options

Mod

Description

A09

Line Reactor

Includes an integrally-mounted AC line reactor factory-
installed and -wired between the circuit breaker disconnect
means and the power converter for high-true power factor
and effective harmonic mitigation. It complies with IEEE 519
guidelines. Optional for 1 to 20 HP 460 Vac and 1 to 10 HP
208/230 Vac models, but included for 25 to 100 HP 460 Vac
and 15 to 50 HP 208/230 Vac models.

B09

Line Contactor

Provides a line contactor factory-wired between the circuit
breaker disconnect (or line reactor, when provided) and the
power converter.

C09

3 to 15 PSI Transducer with Digital Display

Provides the controller with the capability to follow a user
supplied 3 to 15 PSI follower signal. The module is calibrated
to operate as a 4-20 mA DC follower for the power converter.

D09

Omit Keypad Display

Omits keypad display from the door of the controller. A
separate keypad must be ordered to program the drive
controller.

E09

Smoke Purge

Provides smoke purge operating mode controlled by a user-
supplied 120 Vac signal. When power is supplied to the user-
supplied contact, motor operation is transferred to:

• 60 Hz operation if Power Circuit W is supplied.

• Bypass across the line operation if Power Circuit Y is

supplied.

G09

22 kAIC UL Coordinated Rating

Provides fully-coordinated 22 kAIC rating marked on the
enclosure nameplate (short-circuit coordination to UL508C
Power Conversion Equipment and NEMA ICS 7.1).

H09

Analog Card

Provides an analog output with a range of 0-20 mA for
customer use. It is factory-programmed for motor frequency,
and includes an analog card with AO and COM wired to the
customer terminal block. Reassignable X-Y range with
keypad display.

J09

0-10 Vdc Auto Speed Reference

Provides controller interface for 0-10 Vdc customer supplied
auto speed reference signal into AI2 input using 0-10 V/
4-20 mA converter with Z = 100 k

Ω.