Controller ratings (continued), Input current ratings, Class 8839 econoflex™ ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 195: Ratings

Advertising
background image

Class 8839 Econoflex™ AC Drives

Ratings

195

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

CONTROLLER RATINGS (CONTINUED)

INPUT CURRENT RATINGS

Class 8839 ATV58 Econoflex Drive Controller Ratings 208 Vac

Drive Controller
Catalog Number

Motor Power

208 Vac 60 Hz (HP)

Maximum Continuous
Output Current (A)

Max. Transient (60 s)
Output Current (A)

Power Converter
Part Number

58EC•2V_

1

4.6 5.1

FLEX58U29M2

58ED•2V_

2

7.5 8.3

FLEX58U29M2

58EE•2V_

3

10.6 11.7

FLEX58U41M2

58EF•2V_

5

16.7 18.4

FLEX58U72M2

58EG•2V_

7.5

24.2 26.6

FLEX58U90M2

58EH•2V_

10

30.8 33.9

FLEX58D12M2

58EJ•2V_

15

46.2 50.8

FLEX58D16M2

58EK•2V_

20

59.4 65.3

FLEX58D16M2

58EL•2V_

25

74.8 82.3

FLEX58D23M2

58EM•2V_

30

88

96.8 FLEX58D28M2

58EN•2V_

40

114

125.4 FLEX58D33M2

58EP•2V_

50

143

157.3 FLEX58D46M2

The • may be A or G; A denotes a Type 12K enclosure, G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.

Power shown is for a carrier switching frequency of 8 kHz. For a switching frequency between 12 and 1 6kHz, select the next largest size drive
controller. If the duty cycle does not exceed 60% (36 s maximum for a 60 s cycle), this is not necessary.

Continuous output current based on NEC table 430-150. The Econoflex controller nameplate rating is per the NEC table, not the current value listed
in the keypad lookup table.

Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 460 Vac

Drive Controller
Catalog Number

Motor Power
460 Vac 60 Hz
(HP)

5 kAIC (0.141 mH)
10 kAIC (0.070 mH)
(A)

22 kAIC
(0.032 mH)
(A)

Factory-mounted Line Reactor

Mod A09

5 kAIC (0.141 mH)
10 kAIC (0.070 mH)
(A)

22 kAIC
(0.032 mH)
(A)

58EC•4V_

1

2.8

3.2

1.8

2

58ED•4V_

2

4.8

5.2

3.5

3.8

58EE•4V_

3

6.5

7.6

4.9

5.7

58EF•4V_

5

10.7

12.6

7.9

9.3

58EG•4V_

7.5

14.3

16.9

11.5

13.2

58EH•4V_

10

18.2

22

12.9

15.6

58EJ•4V_

15

25.3

30.3

22.9

22.9

58EK•4V_

20

32

38.4

25.2

30

58EL•4V_

25

32.7

34.1

32.7

34.1

58EM•4V_

30

38.1

39.8

38.1

39.8

58EN•4V_

40

49.3

51.6

49.3

51.6

58EP•4V_

50

61.8

65.4

61.8

65.4

58EQ•4V_

60

75.2

77.7

75.2

77.7

58ER•4V_

75

96.3

100.8

96.3

100.8

58ES•4V_

100

122.6

129.3

122.6

129.3

Select conductor based on NEC.

The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.

Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.

10 kAIC.

Advertising
This manual is related to the following products: