Description of power terminals, Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 20: Power terminal wire size and torque, Atv58 trx power terminals

Advertising
background image

Altivar

®

58 TRX AC Drives

Description of Power Terminals

©

2000–2003 Schneider Electric All Rights Reserved

20

09/2003

DESCRIPTION OF POWER TERMINALS

As shown in the drawing to the left, the ATV58 TRX power terminal
arrangements differ from model to model. The locations of the power
terminals are shown on pages 18–19. The following tables describe the
characteristics of the power terminals and list maximum wire sizes and
tightening torques for the various ATV58 TRX models.

CONDUIT CONNECTIONS FOR TYPE E AND TYPE F
DRIVE CONTROLLERS

The ATV58 TRX Type E and Type F drive controllers are furnished with four
conduit openings at the bottom of the device. The conduit openings are
closed with Type 1 rated plugs. The holes are intended for input and output
power wiring, control wiring, and connection to external components such as
DB resistors or line reactors. To maintain the enclosure rating, do not remove
the plugs from unused conduit holes. Conduit holes are pre-drilled for the
conduit listed in the table below.

Flexible conduit must be used up to the drive controller to facilitate removal
of the terminal block cover. A minimum of 2 feet is recommended.

Function of Power Terminals

Terminal

Function

Found On

Ground terminal (2 provided on some models). All ATV58 TRX models.

L1
L2

Input power.

All models.

L3

All models except U09M2• and U18M2•

+

Connection for DB module.

Models U09M2• and U18M2•.

PA
PB

Connection for DB resistor.

All models except U09M2•, U18M2•, and
C10N4–C33N4.

U
V
W

Output connections to motor.

All models.

K13
K14

N.O. auxiliary contact on controller’s output
contactor. Maximum rating is 10 A at 600 Vac.

ATV58EU09M2ZU – U90N4FZ4.

Power Terminal Wire Size and Torque

Type FVC, Type H, and Type N Models

Maximum Wire Size

AWG (mm

2

)

Torque
lb-in (N•m)

U09M2, U18M2

14 (1.5)

5.0 (0.55)

U29M2, U41M2, U18N4, U29N4, U41N4

8 (6)

7.5 (0.85)

U54M2, U72M2, U54N4, U72N4, U90N4

8 (6)

7.5 (0.85)

U90M2, D12M2, D12N4, D16N4, D23N4

6 (10)

20 (2.25)

D16M2, D23M2, D28N4, D33N4, D46N4

2/0 (35)

88 (10)

D28M2, D33M2, D46M2, D54N4, D64N4, D79N4

4/0 (70)

170 (19)

C10N4X–C19N4X

500 MCM

375 (42)

C23N4X–C33N4X

Supply crimp style lugs to fit selected wire size.

Type E and Type F Models

All models

10 (4)

5.0 (0.55)

75 °C copper.

Type E and Type F Models

Conduit Hole Size

Conduit Size

Hub Catalog No.

ATV58EU09M2ZU
ATV58EU18M2ZU

7/8 inch

1/2 inch

25211-16102

All other ATV58 Type E and Type F
Drive Controllers

1 and 3/32 inch

3/4 inch

25211-24102

L1 L2

+

U

V W

ATV58*U09M2 - U18M2

L1 L2 L3 PA PB U

V W

ATV58*U29M2 - D12M2
ATV58*U18N4 - D23N4

P

o

wrT

e

rm

sNe

w

.eps

J2B

J2A

ATV58EU09M2ZU and ATV58EU18M2ZU
(single-phase input only)

U

V

W K13 K14 +

2

3

4

5

6

7

8

1

3

2

*

L2 L1

1

L3

* L3 is not used

J2B

J2A

ATV58Exxxxxxx

U

V

W K13 K14 PA PB

2

3

4

5

6

7

8

1

3

2

4

L2 L1

1

L3

ATV58*D16M2 - D46M2
ATV58*U28N4 - D79N4

+

L1 L2 L3

PA PB U

V W

ATV58HC10N4X

PA

U

L1 L2 L3

V W

PA

(+)

PC

()

ATV58HC13N4X–C19N4X

U

V

W

L2 L3

L1

PA

(+)

PC

()

ATV58HC23N4X–C33N4X

U

V

W

L2 L3

L1

PA

(+)

PC

()

PA

ATV58 TRX Power Terminals

Advertising