Description of Control Terminals

21

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

DESCRIPTION OF CONTROL TERMINALS

All ATV58 TRX Type E, Type F, Type H, and Type N models have the same
control terminals, shown in the figure to the left. The locations of the control
terminals varies from model to model as shown on pages 18 and 19.

The control terminal strip contains two pull-apart terminal blocks, one for the
relay outputs and one for the low-level inputs and outputs. The S terminal is
used for the shield connection. Maximum wire size for all control terminals is
14 AWG (1.5 mm

2

). Tightening torque is 3.5 lb-in (0.4 N•m). The

characteristics of the control terminals are shown in the table below.

Terminal Function

Characteristics

R1A
R1B
R1C

R1A to R1C is a N.O. contact. When the
drive controller is powered with no fault,
the contact is closed.

R1B to R1C is a N.C. contact. When the
drive controller is powered with no fault,
the contact is open.

Min.: 10 mA, 24 Vdc
Max. inductive load: 1.5 A for 250 Vac and 30 Vdc
Max. resistive load: 5 A for 250 Vac or 30 Vdc

R2A
R2C

N.O. programmable relay R2

S

Shield connection

COM

Common for logic and analog inputs

AO1

Analog current output
X–Y mA analog output, with X and Y
programmable from 0–20 mA.
Factory setting: 0–20 mA.

Maximum load impedance = 500

Resolution: 0.04 mA (9 bits)
Linearity: +/- 0.1 mA
Accuracy: +/- 0.2 mA
The analog output is updated every 2 mS, maximum.

AI1

Analog input 1 (voltage)
Used for speed reference input

0 to 10 Vdc, Impedance = 30 k

Frequency resolution analog reference:

(high speed/1024) Hz (10 bit)

Accuracy ±1%, linearity ±0.5% of the maximum output

frequency

Sampling time: 5 ms
Optically isolated

+10

Supply for reference potentiometer
(1 to 10 k

)

10 V ± 1%, protected against short circuits and overloads
10 mA maximum

AI2

Programmable analog input
Used for speed reference input or
feedback, depending on configuration.

X to Y mA, with X and Y being programmable from

0 to 20 mA (factory setting: 0 to 20 mA)

Impedance = 100

Frequency resolution analog reference:

(high speed/1024) Hz (10 bit)

Accuracy ±1%, linearity ±0.5% of the maximum output

frequency

Sampling time: 5 ms
Optically isolated

LI1
LI2
LI3
LI4

Programmable logic inputs
Function depends on configuration.

Supplied by +24 Vdc
State 0 if < 5 V, state 1 if > 11 V
Vmax = 30 V
Impedance = 3.5 k

Sampling time: 5 ms
Optically isolated

+24

Power supply for logic inputs

+24 V protected against short circuits and overloads
Minimum 20 V, maximum 30 V
200 mA maximum

ATV58 TRX Control Terminals

R1A

R1B

R1C

R2A

R2C

AO

1

COM

AI1

+10

AI2

LI1

LI2

LI3

LI4

+24

S

T