Ac drive options, Basic “drive” power circuit, Class 8998 motor control centers – Schneider Electric ALTIVAR 58 TRX User Manual

Page 214: Ac drive options and basic drive power circuit

Advertising
background image

Class 8998 Motor Control Centers

AC Drive Options and Basic Drive Power Circuit

214

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

• Keypad frequency reference (in Hz).

• Output power (as a percentage of drive rated power).

• Energy consumed (in kilowatts).

• Run time (in hours).

One normally-open contact indication of drive running (closes on run).

One normally-closed contact indication of drive fault (opens on fault).

Optional analog output for motor current, motor frequency, ramp output, motor power, and motor torque.

AC DRIVE OPTIONS

• Commissioning software for personal computers.

• 24 Vdc analog I/O extension card (tachometer feedback).

• 24 Vdc digital I/O extension card (encoder feedback).

• Modbus

®

plus communication card.

• Unitelway/Modbus communication card.

• Profibus DP communication card.

• Ethernet communication card for Transparent Ready™ integration.

• DeviceNet communication card.

BASIC “DRIVE” POWER CIRCUIT

• Consists of disconnect switch and drive pre-programmed for selected options if applicable.

• Includes current-limiting power fuses, if necessary. Power fuses are UL Class J.

• Unit is UL 845 Listed for 100,000 amperes Short Circuit Current.

• Includes operation keypad/display mounted on front of the unit.

• Pilot devices are optional and are only available as 22 mm Telemecanique type pilot devices (five

devices maximum).

• Control power transformer (480 V/120 V), if necessary, for enclosure ventilation fans is included.

M

CB

or

Disc

Power

Fuse

Drive

8998-003.ar

t

Basic “Drive”
Power Circuit

Advertising