Space requirements, Class 8998 motor control centers – Schneider Electric ALTIVAR 58 TRX User Manual

Page 215

Advertising
background image

Class 8998 Motor Control Centers

Space Requirements

215

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

SPACE REQUIREMENTS

NOTE: In the following tables the horsepower shown is nominal and only for convenience; you should
size the controller by the actual motor full-load amperage.

Variable Torque 480 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
at 460 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

0.5 to 3 hp

5.8

12”

24”

5 to 7.5 hp

13

15”

24”

10 to 15 hp

24

24”

36”

20 to 25 hp

34

27”

36”

30 to 50 hp

65

45”

45”

60 to 100 hp

124

72” (20” wide)

72” (20” wide)

125 hp

156

72” (25” wide)

Not available

150 to 250 hp

302

72” (30” wide)

Not available

300 to 500 hp

590

72” (35” wide)

Not available

Variable Torque 208/240 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
200 / 230 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

1 to 3 hp

11

12”

24”

5 hp

18

15”

24”

7.5 to 10 hp

31

24”

36”

15 to 25 hp

75

45”

45”

30 to 50 hp

143

72” (20” wide)

72” (20” wide)

Constant Torque 480 Vac Altivar 58 TRX AC Drives

NEMA Type 1 and 1A
(Gasketed)

NEMA Type 12

Motor Rated Horsepower
at 460 Vac

Maximum Continuous
Output Current (A)

Space (Height)

Space (Height)

0.5 to 3 hp

5.8

12”

24”

5 to 7.5 hp

13

15”

24”

10 to 15 hp

24

24”

36”

20 hp

33

27”

36”

25 to 50 hp

66

45”

45”

50 to 75 hp

115

72” (20” wide)

72” (20” wide)

100 hp

124

72” (25” wide)

Not available

125 to 200 hp

240

72” (30” wide)

Not available

300 to 400

477

72” (35” wide)

Not available

Advertising