115 vac logic input module (vw3a58275u), Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 31: I/o extension cards, Wire

Advertising
background image

Altivar

®

58 TRX AC Drives

I/O Extension Cards

31

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

AO

1

COM

AI1

+10V

AI2

LI1

LI2

LI3

LI4

+24V

SW1

SW2

SW3

SW4

AO1 COM AI1 +10V

AI2

ACI1 ACI2 ACI3 ACI4 ACCOM

115 V

~

Top of the logic
input module

Control terminal strip

Module
terminal block

NOTE: 115 Vac is
present at these five
terminals.

DC control wiring

AC control wiring

in

p

u

t w

ir

in

g

.e

p

s

115 Vac Logic Input Module Typical Wiring

115 VAC Logic Input Module (VW3A58275U)

The 115 Vac logic input module, catalog number VW3A58275U, makes it
possible to use ATV58 TRX control terminal points LI1, LI2, LI3, and LI4 with
control circuits that require 115 Vac control. The module insolates the
115 Vac signals from the 24 Vdc input signals of the drive controller terminal
strip, without modifying the other signals.

The 115 Vac logic input module is designed for use only on the Type H and
Type N families of ATV58 TRX drive controllers. It requires no special
programming.

Drive controller logic inputs LI1, LI2, LI3, and LI4 retain their functionality
when using this module. These inputs correspond to the module inputs
labeled ACI1, ACI2, ACI3, and ACI4 respectively.

The figure at the left shows typical wiring using four switches, operating on
115 Vac, as inputs to the drive controller. Power is derived from a 115 Vac
power source wired to the switches, then to inputs ACI1–ACI4. The 115 Vac
common must be connected to the ACCOM terminal on the module.

See the table below for electrical specifications. The module accepts
26–16 AWG (0.14–1.3 mm

2

) wire.

ACI1
ACI2
ACI3
ACI4

Frequency

47 to 63 Hz

Input Impedance

28 k

Ω ±

10% @ 25 °C (77 °F)

Maximum Allowable
Voltage Range

0–132 Vrms

Input to Guarantee On
State

90 to 132 Vrms

Input to Guarantee Off
State

a

a. Coupling can cause voltages higher than 50 Vrms, which can turn the

input on or prevent it from turning off.

0 to 50 Vrms

Storage Temperature

-25 to 70 °C (-13 to 158 °F)