ADJUSTMENT PARAMETERS

Adjustment parameters can be viewed and modified when the access locking switch on the keypad
display is not locked (see page 24). Adjustment parameters can be modified with the motor stopped or
running.

Low Speed and High Speed

These frequency limits define the speed range permitted, as shown in the graph to the left. Low speed
is adjustable from 0 to the High Speed setting and is factory set at 0 Hz. High Speed is adjustable from
Low Speed to 500 Hz and is factory set to 50 or 60 Hz, depending on the configuration. The speed
reference input is scaled between Low Speed and High Speed. It is possible to modify the scaling with
the Low Speed Operation parameter.

Low Speed Operation

The Low Speed Operation parameter determines the two limits, High Speed (HSP) and Low Speed
(LSP), that define the speed range permitted by the machine under actual operating conditions. This
function can be used for all applications. The following table describes the three settings that can be
assigned for this function.

Maximum Frequency

Maximum Frequency is used as a maximum speed clamp. The High Speed setting can not be above
the Maximum Frequency setting. Maximum Frequency is adjustable from 40 to 500 Hz and factory set
to 60 Hz or 72 Hz depending on the 50/60 Hz switch configuration.

Acceleration and Deceleration Ramp Times

The ramp times for acceleration and deceleration are determined by the requirements of the application
and the dynamics of the machine. The following table shows the acceleration and deceleration settings.

Electronic Inversion of Output Phase

This parameter can be used to change the direction of motor rotation. This parameter is useful if it is
determined, after the motor wiring has been connected, that the motor is not rotating in the correct
direction.

Normal Mode

Pedestal Mode

Deadband Mode

LSP (Low Speed): From 0 to HSP, preset at 0. HSP (High Speed): from LSP to FMAX, preset at 50/60 Hz
x: configured from 0 to 20 mA, preset at 4 mA

y: configured from 4 to 20 mA, preset at 20 mA

Acceleration

Deceleration

Adjustment from 0.05 to 999.9 s, preset at 3 s.

Adjustment from 0.05 to 999.9 s, preset at 3 s.

0 V

0 mA
x mA

20 mA

10 V

20 mA

y mA
4 mA

High

Speed

Low

Speed

H

iLo

S

p

d.

e

p

s

f (Hz)

LSP

0 V
x mA

10 V
y mA

Ref.

HSP

OpSpd_Nml.eps

f (Hz)

LSP

0 V
x mA

10 V
y mA

Ref.

HSP

OpSpd_Pdstl.eps

f (Hz)

LSP

0 V
x mA

10 V
y mA

Ref.

HSP

OpSpd_Dbnd.eps

f (Hz)

t1

t

50/60

0

A

cc_Ram

p

.e

ps

t

f (Hz)

50/60

0

t1

D

ec_Ram

p

.e

ps

Low Speed and
High Speed Diagram

Advertising
This manual is related to the following products: