Drive address, Reset counters, Configurable i/o functions – Schneider Electric ALTIVAR 58 TRX User Manual

Page 50: Default i/o configurations, Assignable i/o functions, Altivar, 58 trx ac drives

Advertising
background image

Altivar

®

58 TRX AC Drives

Configurable I/O Functions

©

2000–2003 Schneider Electric All Rights Reserved

50

09/2003

Drive Address

This parameter is used to set the address when controlling the drive controller by a Modbus device via
the RS-485 port. The baud rate is selectable as 9600 or 19,200 bits/sec.The range of addresses is 0 to
31. The factory setting is 0, indicating that the drive controller is not being controlled via the RS-485 port.

Reset Counters

This parameter can be used to reset the watt-hour meter or the run time meter back to zero.

CONFIGURABLE I/O FUNCTIONS

Configurable I/O Functions can be viewed and modified only when the access locking switch on the
keypad display is in the total unlock position (see page 24). These parameters can be modified only
when the motor is stopped.

Default I/O Configurations

Selecting a macro-configuration automatically assigns the inputs and outputs to functions suitable for
the application. The table below shows the drive controller I/O assignment as a function of the macro-
configuration selected.

Assignable I/O Functions

The table below shows the possible I/O assignments for the ATV58 TRX Type H drive controller and the
optional I/O Extension Cards. Only one I/O extension card or one communication card can be installed
in the drive.

The following I/O are on the drive controller.

• Logic Input 1 (LI1) is configured for Run Forward when the drive controller is set for two wire control

and configured for STOP when the drive controller is set for three wire control.

• Relay Output 1 (R1) is configured as a fault relay (1 N.O. contact and 1 N.C. contact) and cannot be

re-assigned.

Factory-Configured Functions for the Three Macro-Configurations

Material Handling

[1]

General Use

Variable Torque

Basic I/O

Logic input LI1

Forward

Forward

Forward

Logic input LI2

Reverse

Reverse

Reverse

Logic input LI3

2 preset speeds

Jog operation

Auto-Manual

[3]

Logic input LI4

4 preset speeds

Freewheel stop/Run permissive

[2]

DC injection braking

[3]

Analog input AI1

Reference summing

Reference summing

Speed reference 1

[3]

Analog input AI2

Reference summing

Reference summing

Speed reference 2

[3]

Analog output AO1

Motor frequency

Motor frequency

Motor frequency

Relay R1

Drive fault relay

Drive fault relay

Drive fault relay

Relay R2

Output contactor control

Motor thermal state attained

Frequency reference attained

[3]

Analog or Digital I/O Extension Cards

Logic input LI5

8 preset speeds

Fault reset

Freewheel stop

Logic input LI6

Fault reset

Current limit

Ramp switching

Analog input AI3 (analog I/O card)
or
Encoder Inputs (digital I/O card)

Summing speed reference

Summing speed reference

PI regulator

Speed regulation

Speed regulation

Speed regulation

Logic output LO

Current threshold attained

Output contactor control

High speed attained

Analog output AO

Motor current

Motor current

Motor current

[1] Factory default setting for 100 hp products and below.
[2] If the Freewheel Stop/Run Permissive function is configured, the drive controller will not start the motor unless the logic input is connected to +24 V.
[3] For 125–500 hp controllers, the factory settings are:

LI3 = fault reset; LI4 = Not assigned; AI1 = Reference summing; AI2 = Reference summing; R2 = Drive running.