Fault Management Parameters

65

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

FAULT MANAGEMENT PARAMETERS

The ATV58 TRX drive is equipped with features that are designed to protect the drive controller and
motor, and to provide process related information. Understanding the fault management capabilities of
the drive controller and determining the proper configuration for the application can enhance the total
system installation and performance over the life of the equipment. The fault messages provided by the
drive controller can be divided into three categories:

• Protective faults are displayed when the drive detects conditions that may damage the drive controller

and/or motor. The drive controller shuts down to prevent further damage from occurring.

• Drive faults are displayed when a problem in the drive needs to be diagnosed.

• Process faults are displayed when a process signal used by the drive controller is interrupted.

Fault Relay

The fault relay (R1) provides 1 normally open and 1 normally closed contact. The relay is energized and
the state of the contacts reverses when the drive controller is powered up and a fault is not present. This
relay cannot be re-assigned.

Resetting a Fault

The drive controller can be reset after a fault by one of three methods:

• Turning power to the drive controller off, wait for the LEDs to go off, and apply power.

• Using the reset button on the keypad, if programmed for local control, or by a logic input assigned to

Fault Reset.

• By the Automatic Restart function if configured.

Automatic Restart

This function permits automatic restarting after the drive controller detects a fault, provided that the other
operating functions are correct, a Run command is present, and the fault has disappeared. The factory
setting for this function is NO. The number of restart attempts and the delay between these attempts is
selectable.

When the Auto restart is selected, the fault relay remains energized so that the drive controller does not
signal a fault from a condition from which it may be able to restart. If the fault has disappeared, the drive
controller will attempt to restart the motor after the delay time configured. The auto restart delay time is
factory set at 30 seconds and has an adjustable range of 0.1 to 999.9 seconds. If the drive controller
remains faulted after attempting the configured number of restarts, the fault relay will then deenergize.
The drive controller must be reset by cycling power after the cause of the fault has been eliminated. The
number of restart attempts is factory set at 5 and has an adjustable range of 0 to 255.

Fault Messages

Protective Faults

Drive Faults

Process Faults

Input phase loss

Precharge fault

Loss of 4-20 mA signal

Undervoltage

EEPROM fault

Loss of RS-485

Overvoltage

Internal fault

External fault

Drive overheating

Internal communication fault

Speed feedback fault

Motor overload

Power rating error

Communication network fault

Overbraking

Option error

Motor phase loss

Option removed

Overcurrent

EEPROM checks

Motor short circuit

Motor overheating

Thermal sensor fault

Overspeed

Ramp not followed

R1A

R1B

R1C

F

a

ul

t R

e

la

y.

ep

s

Fault Relay Diagram