Drive configuration registers (continued), Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 79: Communication parameters, Drive configuration registers, General configuration registers (continued)

Advertising
background image

Altivar

®

58 TRX AC Drives

Communication Parameters

79

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

W16
or 16#5FE0/10

TBR

Communication speed through the RS-485 port

7 = 9600 baud
8 = 19200 baud

W17
or 16#5FE0/11

RPR

Reset kWh or total running time

0 = No
1 = APH: Reset to 0 the kWh
2 = RTH: Reset to 0 the total running time

Drive Configuration Registers

Word

Code

Units

Description

Possible Values or Range

W50
or 16#5FE1/1

SFT

Switching frequency range.
Adjusting this parameter changes the following
parameters to the factory setting:
SFR (W51)•NCR (W54)
NRD (W60)•CLI (W72)
ITH (W258)•IDC (W270)
IBR (W277)•CTD (W282)

0 =LF: Low frequency
1 =HF1: High frequency without derating.
If th

95%, switch to 4 kHz.

If th < 70%, return to SFR frequency.
2 =HF2: High frequency with derating by one rating

W51
or 16#5FE1/2

SFR

PWM switching frequency
(Values 5 and 6 are not on all drive ratings)

0 = 0.5 kHz if SFT = LF
1 = 1 kHz if SFT = LF
2 = 2 kHz if SFT = LF
3 = 4 kHz if SFT = LF
4 = 8 kHz if SFT = HF1 or HF2
5 = 12 kHz if SFT = HF1 or HF2
6 = 16 kHz if SFT = HF1 or HF2

W52
or 16#5FE1/3

TFR

0.1 Hz

Maximum output frequency

If SFR = 0.5 kHz: 10.0 to 62.0
If SFR = 1 kHz: 10.0 to 125.0
If SFR = 2 kHz: 10.0 to 250.0
If SFR = 4 kHz: 10.0 to 500.0
If SFR = 8 kHz: 10.0 to 500.0
If SFR = 12 kHz: 10.0 to 500.0
If SFR = 16 kHz: 10.0 to 500.0

W53
or 16#5FE1/4

FRS

0.1 Hz

Nominal motor frequency

100–5000 (10.0 to 500.0 Hz)

W54
or 16#5FE1/5

NCR

0.1 A

Nominal motor current

0.25 INV to 1.36 INV
(INV = drive controller nominal current)

W55
or 16#5FE1/6

UNS

1 V

Nominal motor voltage

ATV58•••M2: 200 to 240
ATV58•••N4: 200 to 500
ATV58F•••N4: 200 to 500

W56
or 16#5FE1/7

NSP

1 rpm

Nominal motor speed

0 to 32767

W57
or 16#5FE1/8

COS

0.01

Motor cosine Phi (power factor)

0.50 to 1.00

W58
or 16#5FE1/9

TLI

1%

Torque limit

0 to 200

W59
or 16#5FE1/A

TUN

Auto-tune of motor

0 = No: auto-tune not performed
(value from internal table used).
If written to 0: return to value from table
1 = Yes: auto-tune command
2 = Done: auto-tune performed

W60
or 16#5FE1/B

NRD

Motor noise reduction by switching frequency
modulation

0 = No
1 = Yes

W61

[1]

or 16#5FE1/C

NLD

Energy saving function
(VT macro only)

0 = No
1 = Yes

W62
or 16#5FE1/D

RPT

Type of acceleration and deceleration ramps

0 = LIN: Linear
1 = S: S-shaped
2 = U: U-shaped
3 = CUS: Customized (Type FVC only)

W63
or 16#5FE1/E

DCF

1

Deceleration reduction coefficient used with Fast
Stop: DEC

÷

DCF = Fast Stop ramp

1 to 10

W64
or 16#5FE1/F

BRA

Deceleration ramp adaptation

0 = No
1 = Yes

W65
or 16#5FE1/10

FRT

0.1 Hz

Ramp switching threshold (switch to AC2 and DE2
if output frequency > FRT and FRT

0)

0 to HSP

W66
or 16#5FE1/11

BER

Reserved

W67
or 16#5FE1/12

ADC

Automatic DC injection on stop; or, for Type FVC
only, if CTR = FVC, zero speed is maintained

0 = No
1 = Yes

W68
or 16#5FE1/13

PLS

1

Number of pulses per encoder revolution (For
encoder feedback
I/O card)

1 to 1024

W69

[1]

or 16#5FE1/14

PCC

0.1

Motor power load coefficient (in the event of motor
switching)

2 to 10 (0.2 to 1.0)

[1]

This parameter does not exist for ATV58 Type FVC drive controllers.

General Configuration Registers (Continued)

Word

Code

Units

Description

Possible Values or Range