Ratings, Altivar, 58 trx ac drives – Schneider Electric ALTIVAR 58 TRX User Manual

Page 8: Type h drive controllers

Advertising
background image

Altivar

®

58 TRX AC Drives

Type H Drive Controllers

©

2000–2003 Schneider Electric All Rights Reserved

8

09/2003

Ratings

ATV58 TRX Type H drive controllers may be rated for constant torque (CT), variable torque (VT), and
variable torque low noise (VTLN) applications.

• CT applications usually require 100% of motor-rated torque through the entire speed range, high

transient torque capability, and speed regulation.

• VT applications, such as centrifugal fans and centrifugal pumps, do not require high transient torque

capability. This typically allows a drive to be rated for additional horsepower and additional current as
compared to the constant torque rating.

• VTLN applications, such as centrifugal fans and centrifugal pumps, do not require high transient

torque capability. However, this rating uses a higher switching frequency for quieter motor operation.
As a result, the drive may be rated at the same horsepower and current as the constant torque rating,
particularly at large horsepower sizes.

The 125–500 hp drive controllers are listed in this catalog with ratings typically used for VT applications.
With proper selection, this range of controllers can also be used in CT applications, such as
compressors, conveyors, and extruders, where high performance is not required at low speeds. The
125–500 hp product ratings in this catalog are for applications that require 100% rated torque down to
6 Hz. If the application requires more than 110% transient torque for one minute, select the appropriate
horsepower product. For assistance with selecting the proper AC drive controller for constant torque
applications, consult your local Square D drives specialist.

Application information is also available in product data bulletin SC100, Adjustable Frequency
Controllers Application Guide
, available at www.SquareD.com, or the NEMA Standards Publication:
Application Guide For AC Adjustable Speed Drive Systems.

Ratings for ATV58 TRX Type H Constant Torque; 208/230 Vac, Single-Phase Input with 3-Phase Output;
Switching Frequency at 4 kHz

Frame Size

Drive Controller
Catalog Number

Motor Power
208/230 Vac

Rated
Output Current

Transient
Output Current

Total Dissipated
Power at Rated Load

kW

HP

A

A

W

1

ATV58HU09M2ZU

0.37

0.5

2.3

3.1

42

1

ATV58HU18M2ZU

0.75

1

4.1

5.6

64

2

ATV58HU29M2ZU

1.5

2

7.8

10.6

107

2

ATV58HU41M2ZU

2.2

3

11

15.0

156

3

ATV58HU72M2ZU

3

4

13.7

18.6

160

4

ATV58HU90M2ZU

4

5

18.2

24.8

176

4

ATV58HD12M2ZU

5.5

7.5

24.2

32.9

204

Ratings for ATV58 TRX Type H Variable Torque, Low Noise; 208/230 Vac, Single-Phase Input with 3-Phase Output;
Switching Frequency: ATV58HU09M2–D12M2 at 8 kHz; ATV58HD16M2–D46M2 at 4 KHz

Frame Size

Drive Controller
Catalog Number

Motor Power
208/230 Vac

Rated
Output Current

Transient
Output Current

Total Dissipated
Power at Rated Load

kW

HP

A

A

W

1

ATV58HU09M2ZU

0.37

0.5

2.5

2.8

42

1

ATV58HU18M2ZU

0.75

1

4.8

5.3

64

2

ATV58HU29M2ZU

1.5

2

7.8

8.6

107

2

ATV58HU41M2ZU

2.2

3

11

12.1

156

3

ATV58HU72M2ZU

3

4

14.3

15.7

160

4

ATV58HU90M2ZU

4

5

17.5

19.3

176

4

ATV58HD12M2ZU

5.5

7.5

25.3

27.8

204

6

ATV58HD16M2XZU

7.5

10

30.8

33.9

323

6

ATV58HD23M2XZU

11

15

46.2

50.8

550

7

ATV58HD28M2XZU

15

20

60

66.0

745

7

ATV58HD33M2XZU

18.5

25

75

82.5

895

7

ATV58HD46M2XZU

22

30

88

96.8

900

Refer to page 127 for a

complete list of catalog
numbers. An “X” in the
catalog number indicates that
the product does not have an
internal EMC filter. If an
internal EMC filter is required,
delete the “X” from the
catalog number.

When these drive controllers

are used with a single-phase
input, a line reactor (3%
minimum) must be used.

Refer to page 127 for a

complete list of catalog
numbers. An “X” in the
catalog number indicates that
the product does not have an
internal EMC filter. If an
internal EMC filter is required,
delete the “X” from the
catalog number.

When these drive controllers

are used with a single-phase
input, a line reactor (3%
minimum) must be used.

Advertising