Altivar

®

58 TRX AC Drives

Communication Parameters

©

2000–2003 Schneider Electric All Rights Reserved

82

09/2003

W113
or
16#5FE2/E

AO1

Assignment of
analog output
AO1
(Only on ATV58
Type FVC drive
controllers)

0 = NO: Not assigned
1 = OCR: Motor current
2 = OFR: Motor speed
3 = ORP: Ramp output
4 = TRQ: Motor torque
5 = STQ: Signed motor torque
6 = ORS: Signed ramp output

7 = OPS: PID reference
8 = OPF: PID feedback
9 = OPE: PID error
10 = OPI: PID integral
11 = OPR: Motor power output
12 = THR: Motor thermal state
13 = THD: Drive thermal state

Fault Configuration Registers

Word

Code

Description

Possible Values or Range

W150
or 16#5FE3/1

ATR

Automatic restart

W151
or 16#5FE3/2

OPL

Motor phase loss

W152
or 16#5FE3/3

IPL

Input phase loss

W153
or 16#5FE3/4

THT

Motor thermal protection

W154
or 16#5FE3/5

LFL

Loss of follower

W155
or 16#5FE3/6

FLR

Catch a spinning load

W156
or 16#5FE3/7

STP

Controlled stop on loss of input power

W157
or 16#5FE3/8

SDD

Ramp not followed

W158
or 16#5FE3/9

RST

Type of reset

W159
or 16#5FE3/A

LFF

0.1 Hz

Default speed if 4–20 mA follower signal is lost.

W160
or 16#5FE3/B

EPL

Response to external fault input issued by logic
input

1 = Yes: Immediate fault
3 = LSF: Stop followed by fault indiction

W161
or 16#5FE3/C

ACB

Electronic output phase inversion

0 = No
1 = Yes

Adjustment Registers

Word

Code

Units

Description

Possible Values or Range

W250
or 16#5FE5/1

HSP

0.1 Hz

High speed

LSP to TFR

W251
or 16#5FE5/2

LSP

0.1 Hz

Low speed

0 to HSP

W252
or 16#5FE5/3

ACC

0.1 s
or
0.01 s

Acceleration
(time between 0 and FRS)

0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for Type FVC.

W253
or 16#5FE5/4

DEC

0.1 s
or
0.01 s

Deceleration
(time between FRS and 0)

0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for Type FVC.

W254
or 16#5FE5/5

UFR

1%

IR compensation
(adjustment of auto-tune value)

0 to 150 if SPC = No
0 to 800 if SPC = Yes
0 if CFG = VT

W255
or 16#5FE5/6

FLG

1%

Frequency loop gain

0 to 100

W256

[1]

or 16#5FE5/7

PFL

1%

V/F ratio profile

0 to 100 if CFG = VT
100 if CFG = HDG or GEN

W257
or 16#5FE5/8

STA

1%

Frequency loop stability

0 to 100

W258
or 16#5FE5/9

ITH

0.1 A

Current setting for motor thermal protection

0.25 to 1.36
x INV (drive controller nominal current)

W259
or 16#5FE5/A

SLP

1%

Slip compensation

0 if CFG = VT
0 to 150 if CFG = HDG or GEN

W260
or 16#5FE5/B

AC2

0.1 s
or
0.01 s

Acceleration 2
(time between 0 and FRS)

0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for Type FVC.

W261
or 16#5FE5/C

DE2

0.1 s
or
0.01 s

Deceleration 2
(time between FRS and 0)

0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for Type FVC.

[1]

This parameter does not exist for ATV58 Type FVC drive controllers.

I/O Configuration Registers (Continued)

Word

Code

Description

Possible Values or Range

[1]

Values specific to ATV58 Type FVC models

Advertising