Mounting in a General-Purpose Metal Enclosure

To ensure sufficient air circulation when mounting an ATV58 TRX drive in a general-purpose enclosure,
observe the following:

• Provide ventilation inlets and outlets in the enclosure (see the figure below).

• If the enclosure does not provide sufficient free air flow, install an enclosure ventilation fan with

IP54/NEMA 12 filters to exhaust heat outside of the enclosure (see the figure above). The enclosure
fan should have a greater fan flow rate than the drive controller fan flow rate listed in the table below.

• If there is a possibility of condensation, keep the control supply switched on during periods when the

motor is not running, or install thermostatically controlled strip heaters.

Mounting in a Type 12 or IP54 Metal Enclosure

Certain conditions may require Type 12 or IP54 protection, such as dust, corrosive gas, high humidity
with the risk of condensation and dripping water. When mounting in a Type 12 or IP54 enclosure, follow
the installation recommendations given on page 97.

If the enclosure is non-ventilated, use a stirring fan to circulate the air inside the enclosure to prevent
hot spots from forming. With a stirring fan, the maximum temperature inside the enclosure can then be
up to 60 °C (140 °F), although the current must be derated by 2.2% per °C above 50 °C. If condensation
might form within the enclosure, keep the power supply switched on during periods when the motor is
not running, or install thermostatically controlled strip heaters.

ATV58 TRX Model

Fan Flow Rate

ATV58HU09M2, ATV58U18M2

Non-Ventilated

ATV58HU29M2, ATV58U18N4, ATV58U29N4, ATV58U41N4, ATV58U54N4

36 m

3

/hour

21 CFM

ATV58HU41M2

47 m

3

/hour

27.5 CFM

ATV58HU54M2, ATV58U72M2, ATV58U54N4, ATV58U72N4, ATV58U90N4

72 m

3

/hour

42 CFM

ATV58HU90M2, ATV58D12M2, ATV58D12N4, ATV58D16N4, ATV58D23N4

72 m

3

/hour

42 CFM

ATV58HD16M2, ATV58D23M2, ATV58D28N4, ATV58D33N4, ATV58D46N4

161 m

3

/hour

94 CFM

ATV58HD28M2, ATV58D33M2, ATV58D46M2, ATV58D54N4, ATV58D64N4, ATV58D79N4

343 m

3

/hour

200 CFM

ATV58HC10N4X

600 m

3

/hour

350 CFM

ATV58HC13N4X, C15N4X, C19N4X

900 m

3

/hour

525 CFM

ATV58HC23N4X, C25N4X, C28N4X, C31N4X, C33N4X

900 m

3

/hour

525 CFM

with fan and filter

mounted on enclosure

free air flow

VentEnc.eps