Basic cabling requirements – Simrad EQ60 User Manual

Page 174

Advertising
background image

Simrad EQ60

162

857-164342 / Rev.C

Basic cabling requirements

Cable trays

All permanently installed cables associated with the system
must be supported and protected along their entire lengths using
conduits and/or cable trays. The only exception to this rule is
over the final short distance (max. 0.5 metre) as the cables run
into the cabinets/units to which they are connected. These short
unsupported lengths are to allow the cabinets to move on their
shock mounts, and to allow maintenance and replacements.

• Wherever possible, cable trays must be straight, accessible

and placed so as to avoid possible contamination by
condensation and dripping liquids (oil, etc.). They must be
installed remote from sources of heat, and must be protected
against physical damage. Suitable shields must be provided
where cables are installed in the vicinity of heat sources.

• Unless it is absolutely unavoidable, cables should not be

installed across the vessel’s expansion joints. If the situation
is unavoidable, a loop of cable having a length proportional
to the possible expansion of the joint must be provided. The
minimum internal radius of the loop must be at least twelve
times the external diameter of the cable.

• Where a service requires duplicate supply lines, the cables

must follow separate paths through the vessel whenever
possible.

• Signal cables must not be installed in the same cable tray or

conduit as high-power cables.

• Cables containing insulation materials with different

maximum-rated conductor temperatures should not be
bunched together (that is, in a common clip, gland, conduit or
duct). When this is impractical, the cables must be carefully
bunched such that the maximum temperature expected in any
cable in the bunch is within the specifications of the
lowest-rated cable.

• Cables with protective coverings which may damage other

cables should not be bunched together with other cables.

• Cables having a copper sheath or braiding must be installed

in such a way that galvanic corrosion by contact with other
metals is prevented.

• To allow for future expansion of the system, all cables should

be allocated spare conductor pairs. Also, space within the
vessel should be set aside for the installation of extra cables.

Advertising