2 environmental conditions, Environmental conditions – Liebert Series 600T User Manual

Page 124

Advertising
background image

118

Specifications and Ratings

5.2

Environmental Conditions

Enclosure:

The UPS is housed in a NEMA-1 enclosure. The enclosure is
designed for indoor use only and is not to be subjected to falling
objects or precipitation.

Recommended Operating
Temperature:

25°C

Maximum Operating Temperature:

40°C (design temperature) without derating

Minimum Operating Temperature:

0°C

Storage Temperature:

-

20°C to 70°C

Typical Battery Temperature
Requirements:

Average annual temperature shall not exceed 27°C. Peak
temperature shall not exceed 43°C during any 24

-

hour period. See

battery manufacturer’s recommendations.

Relative Humidity:

0 to 95% without condensation

Operating Elevation:

Sea level to 1219 meters (4000 ft.) without derating

Storage Elevation:

Sea level to 12,192 meters (40,000 ft.)

Audible Noise:

69 dBA typical, measured 5 feet from unit

Derating for Higher Ambient
Temperatures:

91% at 45°C

82% at 50°C

73% at 55°C

Consult your Liebert sales representative regarding applications in
high ambient temperatures. Special temperature sensors must be
installed at the factory.

Derating for Higher Elevations:

95% at 2000 meters

94% at 2200 meters

93% at 2400 meters

92% at 2600 meters

91% at 2800 meters

90% at 3000 meters

NOTE
This category of electronic equipment is agency rated for use in an atmosphere free of
conductive particles. Some industrial facilities may require a room air filtration
system to keep the UPS free of excess moisture and contaminants.

The UPS system is designed to operate continuously at 40°C. However, design
equipment life expectancy will be extended with lower temperatures (25°C is
recommended).