Figure 27 battery cycle monitoring summary screen, Figure 27, Battery cycle monitoring summary screen – Liebert Series 600T User Manual

Page 53: Figure 28

Advertising
background image

Operation

47

Active Cycle Time in place of Accumulated Battery Time, and shows Active Battery AH and Active Battery
kWH instead of accumulated values.

Figure 27 Battery Cycle Monitoring Summary Screen

Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information can be col-
lected remotely, through the optional communications board and modem, by a remote terminal or a personal
computer equipped with a modem and communications program. See 3.1.14 - Communication Interfaces for
more information.

Figure 28 Typical Data on Discharge Cycles of 91 to 240 Seconds Duration During the Recording

Period

NOTE

This information is applicable to systems with separate batteries for each module. If
the modules share a common battery, select one module to do the monitoring and
disregard the other(s).

7

15 min. 32 sec.
71
34
25°C / 77°F

Total No. of Cycles . . . . . . . . . . . . .
Accumulated Battery Time . . . . . . .
Accumulated Battery AH . . . . . . . .
Accumulated Battery KWH . . . . . . .
Battery Temperature . . . . . . . . . . . .

Battery Cycle Monitoring Summary

EXIT

SELECT :

EXIT

Event

Date

Time

Duration

Min. Volt

Max. Amp Start KW Start Temp

15

4/12/95

10:31

235

477

110

70

68

12

3/25/95

20:21

98

479

97

37

65

9

3/13/95

7:35

139

467

173

69

67

5

2/07/95

17:22

199

478

95

40

70

2

11/24/94

12:33

95

477

83

39

69

Total

91-240 se c. Cycl

5

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

Advertising