5 one module off-line, Figure 52 one module off-line (load on ups), One module off-line – Liebert Series 600T User Manual

Page 89: Figure 52, One module off-line (load on ups), Scct, Operation 83

Advertising
background image

Operation

83

3.2.5

One Module Off-Line

A multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the typical con-
figuration. A redundant system includes one more module than the number required to supply the critical load. A
redundant system operates in the redundant mode if all modules are ON LINE. Note that the UPS system can
also operate in the redundant mode with one module OFF LINE if the critical load is reduced so that not all ON
LINE
modules are required. The UPS modules share the load, and the critical load will remain on the UPS sys-
tem if any one of the modules is disconnected (goes OFF LINE) for maintenance or because of an internal fault.

The system control logic monitors the connected critical load and the number of UPS modules ON LINE. If the
UPS system is operating in the redundant mode, the REDUNDANT status message will be displayed at the Sys-
tem Control Cabinet (SCC). If the UPS system is operating in the non-redundant mode (redundant module is
OFF LINE or was not included in the system configuration), the NON-REDUNDANT status message is dis-
played at the SCC. In the Non-Redundant mode, the critical load will be transferred to bypass if any UPS module
goes OFF LINE, and you must transfer the load to bypass in order to perform maintenance on any UPS module.

Figure 52 One Module Off-Line (Load on UPS)

BIB

SKRU

MIB

MBB

I

R

#2

UPS

CB1

CB2

System

Controls

RIB

RIB

RIB

BFB

Output

SBB

SBS

RIB

RIB

RIB

BFB

I

R

#1

UPS

CB1

CB2

I

R

#3

UPS

CB1

CB2

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD

Advertising