Liebert Series 600T User Manual

Page 127

Advertising
background image

Specifications and Ratings

121

CRITICAL LOAD OUTPUT

Output Voltage:

Standard voltages—208Y/120 VAC, 480Y/277 VAC, 600Y/346 VAC. Other
voltages available on request.
SCC output: 3

-

phase, 3

-

wire plus ground or 3

-

phase, 4

-

wire plus ground.

Module output to SCC: 3

-

phase, 4

-

wire plus ground (neutral required).

Optional voltages—208 VAC, 480 VAC, 600 VAC. Other optional voltages
available on request. 3

-

phase, 3

-

wire plus ground (ungrounded or corner

grounded delta).

Voltage Regulation:

±0.5% for balanced load.
±2% for unbalanced load.

Voltage Adjustment Range:

±5% manually.

Line Drop Compensation Range:

Up to +5% automatic load dependent.

Frequency

59.5 Hz to 60.5 Hz.

Slew Rate:

0.06 Hz per second.

Phase Balancing:

120° ±1° for balanced loads.
120° ±3° for 50% unbalanced loads.

Voltage Imbalance:

20% Unbalanced Load
50% Unbalanced Load

±1% from the arithmetic average of the 3 phases.
±2% from the arithmetic average of the 3 phases.

Voltage Transient:

20% Load Step
30% Load Step
100% Load Step
Loss or Return of AC Input Power
Manual Transfer of 100% Load

±4% from the average peak voltage.
±5% from the average peak voltage.
±7% from the average peak voltage.
±1% from the average peak voltage.
±4% from the average peak voltage.

Voltage Transient Recovery Time:

To within 1% of steady state output voltage within 50 milliseconds.

Voltage Harmonic Content:

Maximum 5% RMS total, for any combination of linear and nonlinear loads.
Maximum 3% RMS single, for linear loads.

Module Overload Capacity at Full
Output Voltage:
(System overload capacity depends
on the configuration of on-line
modules.)

104% of full load rating continuously.
125% of full load rating for 10 minutes.
150% of full load rating for 30 seconds.
(with ±2% voltage regulation).

Fault Clearing:

300% of normal full load current subcycle.
1000% of normal full load current up to 40 milliseconds with bypass available.