Operation

3.2.6

Off Battery

The battery plant can be disconnected from the UPS modules, if required for battery maintenance, by opening the
module battery disconnect (MBD) circuit breaker(s). In this situation the UPS system will continue to supply
conditioned power to the critical load, but if input power fails, the UPS system cannot supply power to the load.

Figure 53 Load on UPS (Battery Not Available)

!

CAUTION

When the UPS system is operating with the module battery disconnect (MBD)
circuit breaker(s) open, the critical load is not protected from loss of the utility
source power.