3.1.13 Alarm and Status Messages

Module Status Messages

The module status messages indicate how many UPS modules are included in the system and the present status
of each module.

The following status messages may appear in the module status area.

1.

MOD N. A module status message line is displayed for each UPS module in the system. Up to six (6)
modules may be included in a multi-module system. The N in the message will indicate a specific UPS
module number, 1 through 6.

2.

ON LINE. The UPS module output circuit breaker is closed and power from the module is available to the
SCC. The module output is sharing the critical load if the UPS Output Breaker is closed.

3.

OFF-LINE. The UPS module output circuit breaker is open. More specific alarm messages are displayed at
the UPS module.

4.

SUM ALM. The Module Summary Alarm has been activated by one of the alarm messages listed in two
tables

SCC and Module Remote Monitor Indications and Other Alarms That Activate Summary

Alarms

in 3.1.5 - System Configuration Screens. The specific alarm message is displayed at the UPS

module.

5.

COM FAIL. The UPS module is not communicating with the SCC. This could mean loss of power to the
UPS module controls, a disconnected cable, or a control logic failure (detected by watchdog timer. Call
Liebert Global Services if you require assistance. To resume communication after control power is restored,
sequence display to Master Menu.

Figure 46 SCC Status and Alarm Message Areas

UPS RATINGS

LOAD

Byp Not Avail
Static Sw Unable
Module Sum Alm

UPS INPUT PWR

BYPASS INPUT

A-B

B-C

C-A

0V

0V

0V

0 Hz

0V

0V

0V

A-B

B-C

C-A

Not OK to Transfer
Static Switch Connected

MOD 1 ON LINE SUM ALM
MOD 2 ON LINE SUM ALM
MOD 3 ON LINE SUM ALM

A-B

B-C

C-A

480V

480V

480V

60.0 Hz

SCCT 1600

OUTPUT VOLTAGE

627 KVA / 502 KW

755A

755A

755A

3 OF 3 MODULES

CONNECTED
REDUNDANT

A

B

C

Time To Overload
Transfer: XXXX SEC

LOAD BLOCK

MESSAGES

ALARM

MESSAGES

MODULE STATUS

MESSAGES

SYSTEM STATUS

MESSAGES