6 options, Options – Liebert Series 600T User Manual

Page 18

Advertising
background image

12

Introduction

1.6

Options

A number of standard pre-designed options are available from Liebert for your UPS system. Described below are
the most frequently provided options. Note that the battery items (1-3) are required to complete the UPS system.
The remaining options provide improved system performance or convenience.

1.

Battery
The batteries provide power in the event of a power outage. The Liebert UPS can use a variety of battery
types, provided the battery plant is designed for the UPS DC voltage range and the load requirements of
your application.

2.

Battery Racks or Cabinets
The battery racks are specifically designed for stationary service batteries. They are painted with electrolyte-
resistant paint for corrosion resistance. Battery cabinets are available for 150 through 600 kVA modules.

3.

Module Battery Disconnect
The UPS system utilizes a separate Module Battery Disconnect for remotely located batteries. A sensing cir-
cuit in the UPS module, set at the battery low voltage limit, trips the Module Battery Disconnect to safe-
guard the battery from excessive discharge. The Module Battery Disconnect has an undervoltage release
mechanism designed to ensure that during any shutdown or failure mode all battery potential is removed
from the UPS system

4.

Input Distortion Filter
This filter reduces rectifier input current reflected harmonic distortion to less than 7% THD, and less than
4% THD for modules with the optional 12-pulse rectifier. The filter is factory installed within the UPS. This
filter also improves the input power factor to better than 0.92 lagging.

5.

12-Pulse Rectifier
Certain models may be ordered with the optional 12-pulse rectifier section. This provides input isolation and
reduces reflected input current THD to less than 9%, or less than 4% with optional input filter.

6.

Isolation Transformers
An optional rectifier input isolation transformer is available in a matching transformer cabinet. A bypass iso-
lation transformer is also available.

7.

Three Breaker Maintenance Bypass
This switchboard provides make-before-break maintenance bypass. It includes: UPS Bypass Input Breaker
(BIB), Maintenance Bypass Breaker (MBB), and Maintenance Isolation Breaker (MIB).

8.

Two Breaker Maintenance Bypass
This switchboard provides make-before-break maintenance bypass. It includes: Maintenance Bypass
Breaker (MBB) and Maintenance Isolation Breaker (MIB).

9.

Load Bus Synchronization (LBS)
The Load Bus Sync (LBS) option keeps two independent UPS systems (and therefore their critical load
buses) in sync, even when the modules are operating on batteries or asynchronous AC sources. This means
that critical loads connected to both load buses through a Static Bus Transfer Switch can be switched seam-
lessly between the two.

10. SiteScan Central Monitoring System

Liebert manufactures a central monitoring system that automatically displays key UPS measurements and
alarms, as well as data from a variety of sensors. This monitoring system signals alarms so corrective action
can be taken. Events and data can be printed in hard copy. Data can be logged for analysis.

11. Remote Monitor Panel

The UPS system may also be provided with an optional Remote Monitor Panel. This Panel provides eight
LED indicators and may be placed at a convenient location near the critical load. A functional description of
the Remote Monitor Panel is provided in 3.0 - Operation of this manual.

12. Customer Alarm Interface

This optional interface board allows the input and display of 8 alarms from customer-supplied contacts, each
with a customer-selected name of up to 16 characters. The following attributes can be user programmed for
each alarm: latching, summary, freeze history, sound horn, auto-dial, and time delay (0 to 999.9 seconds).

Advertising