Auto dial, Figure 32 auto dial setting screen, Figure 32 – Liebert Series 600T User Manual

Page 57: Auto dial setting screen

Advertising
background image

Operation

51

Auto Dial

This is a feature that automatically dials (through a customer supplied PC-compatible modem) a pre-pro-
grammed telephone number (up to 12 digits) when specified alarm conditions occur within the UPS system. The
connection for the modem is at the SCC. Automatic dial attempts to the first number are made at periodic inter-
vals for 30 minutes. If unanswered, the system rolls over to the second number and repeats the process until con-
nection is made.

Upon connection, the system transmits data, in RS-232C format, that includes the system identification code, the
present alarm message(s) and the time that the alarm(s) occurred. Refer to 3.1.14 - Communication Interfaces.

Refer to the Special Functions column in Table 1 to see which alarm messages will initiate an auto-dial call.

Figure 32 Auto Dial Setting Screen

If the auto-dial numbers were specified at time of order or installation, the numbers are pre-programmed into the
system. However, if the numbers need to be changed, follow the steps listed below to reprogram the auto-dialer
at the SCC.

1.

From the System Configuration screen, press the Up or Down pad to move the highlighted cursor to Auto
Dial.

2.

Press the Select pad. The Auto Dial screen will appear.

3.

Move to and select the first Auto Dial Number.

4.

Press the Select pad to move the arrow to the next digit to the right.

5.

When the arrow is on the digit to be changed, press the Up pad to increase the number or press the Down
pad to decrease it. Press Select to set the value and move to the next digit.

6.

After all of the changes have been made, press the Select pad again to return to the System Configuration
screen.

7.

If required, go to the Second Number screen and enter the correct number.

AUTO DIAL SETTING SCREEN

YES
2400
1 800 555 - 1234
0 000 000 - 0000
xxxxxxxxxxxxxxxxxxx

Enable Auto Dial .....................................
Modem Baud Rate ..................................
Auto Dial Number ...................................

Second Number ...............................

Modem Initialization String .....................

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

EXIT