2 modes of operation, 1 load on bypass, Figure 47 load on bypass (ups not available) – Liebert Series 600T User Manual

Page 84: Modes of operation, Load on bypass, Figure 47, Load on bypass (ups not available), Scct

Advertising
background image

78

Operation

3.2

Modes of Operation

This section illustrates the flow of power through circuit breakers, switches, and UPS components during various
modes of operation. An SCCB with three modules is shown. The same modes of operation apply to all configu-
rations of the Liebert Series 600T UPS multi-module system. Highlighted (thick) lines in the diagrams indicate
power flow and power availability.

These illustrations show a three-breaker maintenance bypass because it is most commonly used. Your installa-
tion may have a two-breaker, three-breaker, or four-breaker maintenance bypass, or none at all.

These illustrations do not show an alternate power source (generator) and automatic transfer switch (external to
the UPS) that might be present at your installation.

The following circuit breaker abbreviations are used:

3.2.1

Load On Bypass

Load on Bypass, with the UPS not available, is shown in Figure 47. The UPS system could be in this mode of
operation during either initial start-up or UPS system shutdown and isolation for maintenance.

Figure 47 Load on Bypass (UPS Not Available)

BFB

Bypass Feeder Breaker

BIB

Bypass Input Breaker

CB1

Module Input Breaker

CB2

Module Output Breaker

MBB

Maintenance Bypass Breaker

MBD

Module Battery Disconnect

MIB

Maintenance Isolation Breaker

RIB

Rectifier Input Breaker

SBB

System Bypass Breaker

I

R

#2

UPS

CB1

CB2

I

R

#1

UPS

CB1

System

Controls

I

R

#3

UPS

CB1

CB2

RIB

RIB

BIB

CB2

SKRU

RIB

BFB

MIB

Output

SBB

SBS

MBB

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

SCCT

Battery

MBD

Battery

MBD

Advertising