6

Thermostats are automatic reset for use in a

normally closed circuit where the thermostat is

connected in series with the holding coil of the

magnetic starter. Thermostats provide Over

Temperature Protection 2" in accordance with

NEMA MG 1Ć12.53. When the motor is so marked

locked rotor protection is not provided by the

winding over temperature protector. It is

suggested that over current protection be used

in the motor starter to insure locked rotor

protection.

MOTOR CONTROLLER MAY HAVE AUTO-
MATIC OR MANUAL OVERLOAD RESET.
DISCONNECT ALL POWER LEADS TO
MOTOR WHEN PERFORMING ANY WORK
ON MOTOR OR DRIVEN EQUIPMENT.

A MANUAL, MOMENTARY START
SWITCH IS REQUIRED TO PREVENT AU-
TOMATIC RESTART OF MOTOR WHEN
THERMOSTAT RESETS.

!

WARNING

If current through the thermostat will exceed the

values listed in Figure 2 an intermediate control

circuit relay must be used to reduce the current

or the thermostat will not work properly.

Alternating Current

Volts

Continuous

Amperes

Inrush

Amperes

110Ć120

3.0

30

220Ć240

1.5

15

440Ć480

0.75

7.5

550Ć600

0.6

6.0

FIGURE 2

TYPICAL THERMAL PROTECTOR

WIRING DIAGRAM

MOISTURE DETECTION SYSTEM

MOISTURE SENSING PROBES

Reliance Submersible Pump Motors are

equipped

with

moisture

detection

devices. Failure to properly connect or

utilize this system voids motor warranty.

!

IMPORTANT

Moisture sensing probes, leads marked W

1

, and

W

2

, must be used in conjunction with an

induction relay. This device will detect moisture

entering the oil chamber due to failure of the

outer seal and, when properly connected to a

warning device, will provide notification of

needed maintenance. Integrity of system

requires periodic test.

CONTROLSAND SIGNAL DEVICES
A control and signal device (not supplied by

Reliance) must be installed at the job site to

complete the moisture detection system.

Compatible controls are available from:

Charles F. Warrick Co., Normandy Court,

Royal Oak, Michigan 48073, (810) 549Ć4900.

P1 & P2 Normally Closed Thermostat Leads

(normally open thermostats are not acceptable to UL)

(1) Starter Holding Coil

(2) Holding Coil Contacts - N.O.

THERMOSTATS

MOTOR

P2

P1

T1 T2 T3

GRD

L1

L2

L3

AĆC LINE

AĆC LINE

STARTER

(2)

(1)

P1

P2

STOP

START