Type 2800ćxxx motor moisture detector control – Polaris TBM 200 LH User Manual

Page 43

Advertising
background image

7

CONTROL SELECTION AND ORDERING FOR CHARLES F. WARRICK CO. CONTROLS

Line voltages are nominal values and may be anywhere from nominal minus 15% to nominal plus 10%.

TYPE 2800ĆXXX MOTOR

MOISTURE DETECTOR CONTROL

INSTALLATION
All type 2800ĆXXX controls are identified by a

specific component number which follows the

format 2800ĆXXX where the X's are replaced

by numbers and letters indicative of the AĆC

supply line voltage and frequency, contact

configuration and enclosure. Each control has a

data label on the right hand side of the terminal

block. In addition, each enclosed control has

another data label on the outside of the

enclosure cover.

Mount the control on a vertical surface with the

transformer on the left hand side and accomplish

all indicated wiring. Terminals on the control

are numbered and are in the same relative

position as the terminals shown on the wiring

diagram.

Terminal pair 1Ć2 must be continuously energized

from an AĆC supply line of electrical characterĆ

istics shown on the data label.

Contacts must be wired into the electrical load

circuit(s) of the warningdevices as required.

Each contact used for load duty must be wired

in series with the load and that series branch

circuit connected across a power source

compatible with the load.

Wiringmust be provided from the moisture

detector sensor probe leads of the RELIANCE

ELECTRIC motor designated W1 and W2 to

terminals 9 and 10 of the 2800ĆXXX control.

Control leads should not be installed in the same

conduit as power leads. Induced voltage can

cause false moisture signals.