Lead color coding – Polaris TBM 200 LH User Manual

Page 44

Advertising
background image

8

CONTACT OPERATION
Normally open load contacts close and normally

closed load contacts open when the sensor

probes detect the influx of moisture within the

motor.

TEST PROCEDURE
A normally closed pushbutton and neon

indicating lamp are provided as means of

checking the moisture sensing components.
When the pushbutton is depressed, the

indicating lamp will be illuminated to indicate (A)

power is supplied to the control, (B) the control

is operative, and (C) wiring to the moisture

sensing probes in the motor is intact. This

procedure should be performed periodically to

confirm integrity of circuit.

SIGNAL DEVICES
The signal device may be audible (bell, buzzer,

horn or siren) or visible (incandescent or neon

lamp) or both - a signal device of your choice

may be obtained from your local electrical supply

house.

SYSTEM OPERATION
It is recommended that upon indication (by warnĆ

ing light, etc.,) of outer seal failure that the motor

be removed from the installation and the oil and

outer seal be replaced as soon as possible.
If reconditioning is not performed within a30 day

period it is recommended that the inner seal be

thoroughly inspected and replaced if required.
When ordering parts or reporting trouble give

Sales Office complete Nameplate Data.

A.C.

SUPPLY

LINE

PRIMARY

500 V.

SEC'D.

RELAY

COIL

TEST RESISTOR
MOISTURE SENSORS

NORMALLY OPEN

MOTOR

WIRING BY WARRICK

WIRING BY OTHERS

CONTROL ENCLOSURE

TEST

SWITCH

TEST

LAMP

1

2

3

4

6

5

7

8

10

9

1

A

1

TO SIGNAL CIRCUIT

W

1

W

2

FIGURE 3

MOISTURE SENSING CIRCUIT

TYPICAL WIRING DIAGRAM

LEAD COLOR CODING

BLACK

LEAD

WHITE

LEAD

RED

LEAD

ORANGE

LEAD

GREEN

LEAD

Power

Polyphase

T

1

T

2

T

3

Ċ

Ground

Power

Cable

Single

Phase

T

1

T

4

T

A

Ċ

Ground

Control Cable

All

P

1

P

2

W

1

W

2

Ground

Advertising