SOLA 4000 - PCB Description

JUE 401268

100

IPR front view

FIG. 1.6 illustrates the LEDs, potentiometers, switches and test

sleeves of the IPR pcb that are accessible from the front.

- Parallel Operation On: This inverter is connected with another

or more inverters to the output in parallel.

- Redundancy Not OK: Redundant units only.The load has in-

creased or an inverter is off so that if this unit fails, the system
must transfer to the bypass supply.

- Parallel Fault: A fault has occurred with the regulation of the

inverter in parallel with another inverter.

- SSI pulse generator failure: A failure or loss of synchronism has

occurred within the SSI ON pulse generator. To reset press PB3
and then PB1 on the ICP pcb.

- Reference current for parallel regulation 6Vrms = nominal cur-

rent of the system (0.8 p.f.).

- Inverter output current for parallel regulation 6Vrms = nominal

current of this unit (0.8 p.f.).

- Difference current for parallel regulation

- Output current of this unit. 8Vdc = nominal load current of this

unit (0,8 p.f.)

- System output current. 8Vdc = nominal load current on the sys-

tem (0.8 p.f.)

- Redundancy current. 8Vdc = nominal load current on the re-

mainder of the system (without this unit, 0.8 p.f.)

- Power of this unit. 6Vdc = nominal load power on this unit

- Power of the system. 6Vdc = nominal load power on the system

- Output voltage phase T

- Output voltage phase R-S

- Adjust for 6Vrms at TP1 with nominal load current (0.8 p.f.)

- Adjust for 6Vrms at TP2 with nominal load current (0.8 p.f.)

- Adjust for 8Vdc at TP4 with nominal load current (0.8 p.f.)

- Adjust for 8Vdc at TP5 with nominal load current (0.8 p.f.)

- Adjust for 6Vdc at TP7 with nominal load

- Adjust for 6Vdc at TP8 with nominal load

- Manual: manual switching on/off of the inverter permitted

- Auto: inverter will automatically switch on/off depending on the

load applied and the internal programming of IPR pcb.

LD1 Parall.Operat

LD2 Red not ok

LD3 Parallel Fault

LD4 Pulse gen. Fail

TP2 I

out

=6V

rms

TP3 I

error

TP4 I

load

= 8V

TP5 I

syst

= 8V

TP6 I

red

TP1 I

ref

= 6V

rms

TP7 P

out

=6V

TP8 P

syst

= 6V

P1 I

ref

P2 I

out

P3 I

load

P4 I

syst

P5 P

out

P6 P

syst

Auto

S1

Manual

TP9

TP10

1 UPS Control Logic