4 panel settings – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 86

Advertising
background image

JUE 401267

86

SOLA 4000 - Operating Panel

4

PANEL SETTINGS

4.1 DIP Switch Settings

With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside
the front door , the operating parameters can be set according to
actual conditions.

Note: The following settings apply only with the software V2.0 or
later.

DIP Switch SW1

Dip 1

Dip 2

Dip 3

Dip 4

UPS RATING

(KVA)

OFF

OFF

OFF

OFF

10

ON

OFF

OFF

OFF

15

OFF

ON

OFF

OFF

20

ON

ON

OFF

OFF

30

OFF

OFF

ON

OFF

40

ON

OFF

ON

OFF

60

OFF

ON

ON

OFF

80

ON

ON

ON

OFF

100

OFF

OFF

OFF

ON

120

TAB. 4.1 - Setting of SW1 - UPS rating

DIP Switch SW1

Nominal Voltage

DIP 7

DIP 8

Vnom

OFF

OFF

120

ON

OFF

220

OFF

ON

230

ON

ON

240

TAB. 4.2 - Setting of SW1

TAB. 4.3 - Setting of SW1
Nominal Voltage

DIP Switch SW1

DIP 5

CONFIGURATION

OFF

Not Hot-standby

ON

Hot-Standby

DIP 6

BYPASS - LINE

OFF

Installed

ON

Not installed

4 Panel Settings