1 installation, Sola 4000 - installation and initial start-up, 8 common alarm contacts – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 34: 9 remote reset

Advertising
background image

SOLA 4000 - Installation and Initial Start-Up

JUE 401265

34

1.8 Common Alarm Contacts

As a standard feature, contacts are provided for a remote common
alarm.The connector is located on the control p.c.b for the front
operating panel (CPU/NCP), located inside the front door of the
UPS.

FIG. 1.8.1 Connection of Remote Common Alarm

Nominal Rating of Contacts

125 V

0,5 A

60 W

30 V

2 A

60 W

TAB. 1.8.1 Nominal Rating of contacts for the common alarm.

Note 1: As an option a pcb CP-NET is available, providing more

contacts, compatible with most common configurations (eg AS400,
Novell etc.)
A Remote panel may also be purchased with identical functions to
the front operating panel.

Note 2: To achieve a single common alarm for parallel or hot-

standby units, the contacts of each unit may be interconnected in
parallel (normally - open) or series (normally - closed).

1.9 Remote Reset

The UPS system may be reset remotely with the connection of
contacts ( a push-button) to the terminal M4 as shown:

FIG.1.9.1 Connection of Remote Reset

Note: The cable used must be twisted pair, with a total shield.

This shield must be grounded at one end (the cabinet of the
UPS may be used).