SOLA 4000 - Installation and Initial Start-Up

JUE 401265

37

1.10.1 Installation of the Interconnection Cable

The supplied cable must be connected between the units within the
system. This must be connected at either of the connectors CN12
or CN13 on the mother-board of the Inverter/Bypass electronics
(IBYBP-CP) and the other end of the cable is connected to either
CN12 or CN13 on the mother-board of the Inverter/Bypass elec-
tronics (IBYBP-CP) of the other unit(s).

Note: If the unit is to be added to one already installed stand-alone
unit which has not been previously tested in a hot-standby configu-
ration, the supports and mounting screws to mount the cable to the
p.c.b are supplied with the cable. They must be mounted at both
sides of the selected connector in order to fix the cable securely to
the connector with the supplied screws.

FIG. 1.10.3 Interconnection of control BUS cable for hot-standby units