1 ups control logic, Sola 4000 - pcb description – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 97

Advertising
background image

SOLA 4000 - PCB Description

JUE 401268

97

Inverter control and regulation (parallel configuration)

• parallel regulation of up to 8 inverters

• system control for up to 8 inverters (together with ICP pcb)

• cold-standby control

• load monitoring

• redundancy monitoring

ICP Front View

FIG. 1.3 illustrates the LEDs and switches of the ICP PCB which
are accessible from the front.

- Push to switch the inverter ON/OFF

- Inv. electronic power supply in order: green LED is illuminated

- Defect in the internal quartz oscillator: red LED is illuminated

- RESET

- Inverter in order: green LED is illuminated

- Inv. voltage within tolerance (within +/- 10% of Vnom): green

LED is illuminated

- Retransfer to inv. operation is blocked after 5 attempts within 3

minutes: red LED is illuminated

- Overtemperature within the inv. section: red LED is illuminated

- The inverter static switch has failed to switch ON/OFF: red LED

is illuminated

- All conditions are in order for a retransfer of the load to the inv.

(for hot-standby units, the inv. is ready in case of a failure to
the on-line inv.): green LED is illuminated

- A failure within the monitoring of the output switch: red LED is

illuminated

- Disable the quartz oscillator

- Disable inverter voltage monitoring

1 UPS Control Logic

PB2 Inv. ON / OFF

LD1 PSP OK

LD3 Osc. Failure

PB1 Reset

LD6 Inverter ready

LD7 IUG failure

S1 Osc. Block.

S2 Inverter Monit. Block.

PB3 SSI ON

TP1 INV. Volts

Vnom=6V

LD9 Inverter OK

LD8 Inverter volts OK

LD2 Retr. blocked

LD4 Overtemperature

LD5 SSI failure

P1 INV. Volts

tol.adjust