1 installation, Sola 4000 - installation and initial start-up, 2 installation of external batteries – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 44

Advertising
background image

SOLA 4000 - Installation and Initial Start-Up

JUE 401265

44

1.12.2 Installation of External Batteries

External Battery (38 Ah) Installation

38 Ah external batteries are installed in a B3/38 battery cabinet. To
assemble the battery cabinet:

• Place four battery blocks on the trays of the first level (see FIG.

1.12.2).

• Place six battery blocks on the trays of the second and third

levels (see FIG. 1.12.3).

• Interconnect the blocks in series (block 1 / negative pole ==>

block 2 / positive pole,....)

Warning: after assembly there is a voltage of 48 V on the first
level, and 72 V on the second and third levels.

• If necessary secure with strapping (against vibrations).

• Insert the trays into the battery cabinet as shown in FIG. 1.12.4

FIG. 1.12.4 Battery cabinet B3/38

FIG. 1.12.3 B3/38: battery trays in the
second and the third level

1 Installation

Advertising