1 ups control logic, Sola 4000 - pcb description – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 98

Advertising
background image

SOLA 4000 - PCB Description

JUE 401268

98

- Proportional to the inv. voltage. 6V

nominal inverter voltage

- Inv. voltage tolerance adjust for 6V at TP1 with nom. voltage

- Push to switch ON the inverter output static switch (SSI)

ICT-2 Front View

FIG. 1.4 illustrates the potentiometers, LEDs and test points of

the ICT-2 PCB which are accessible from the front.

- Frequency offset adjustment (when synchronisation is blocked

at TP5)

- Inverter voltage adjustment phase T

- Inverter voltage adjustment phase S

- Inverter voltage adjustment phase R

- Inverter voltage adjustment during test operation (jumpers JP1,

JP2, JP3 in position 2,3)

- Overload on phase T: red LED is illuminated

- Overload on phase S: red LED is illuminated

- Overload on phase R: red LED is illuminated

- Pulse release: green LED is illuminated

- Synchronisation OK: green LED is illuminated

- Synchronisation block

- Test point: test voltage = 6Vdc at full load

- Test point: test voltage = 4Vdc at full load on phase T

- Test point: test voltage = 4Vdc at full load on phase S

1 UPS Control Logic

P1 Freq.

Offset

LD4 Overload

Φ

S

LD3 Overload

Φ

R

LD1 Synch. OK

LD5 Overload

Φ

T

TP1 I

nom

= 4V

Φ

R

TP2 I

nom

= 4V

Φ

S

LD2 Pulse Release

TP4 I

nom

= 6V

TP3 I

nom

= 4V

Φ

T

P7 I

nom

Φ

S

P6 I

nom

Φ

R

P8 I

nom

Φ

T

P5

Φ

T Volts

P4

Φ

S Volts

P3

Φ

R Volts

P2 Manual Test

TP5