SOLA 4000 - Installation and Initial Start-Up

JUE 401265

52

• If your unit has separate supplies for the rectifier and bypass

(terminals 4-L1, 4-L2, 4-L3, 4-N), switch on the external supply
for the bypass. Check that the bypass supply voltage at termi-
nals 4-L1, 4-L2, 4-L3, 4-N is within ±10% of the nominal input
voltage.

If there are no separate input terminals then the bypass input is
the same as that checked previously for the rectifier input.

• Close IUG.

• Close IRE.

?

Does the display on the CPHC16 -S pcb for the bypass give the
indication "P"?

yes

• Open IRE and exchange any two of the cables at the bypass

input terminals 4-L1, 4-L2, 4-L3.

• Return to E.

no

• Are the status LEDs (green) 1, 2, 3, 14, 16, 17, 19, 26, on the

operating panel continuously on?

no:

Check that the mains frequency is in tolerance.

OK?

yes: Is the pcb CPHC16 -S for the bypass
correctly functioning? The display should be
rotating clockwise.

no:

Call for service assistance.

yes: Check again the input supply. Check

that it is in accordance with the UPS
rating label.

no:

The mains frequency must be within
tolerance in order for the bypass to be
availabe

yes:

Continue with F.

F: Synchronisation Check

• Check that the green LED LD1 on the ICT-2 pcb is permanently

lit and there is no "S" indication on the bypass electronics.

• On the SS/FY pcb, measure the voltage between the screws

Bypass R and Inverter R. Then repeat for the other two phases.

?

Are the voltages < 25Vac?

no

• If the voltage is continuously fluctuating from 0 to 400V there is

a synchronisation problem. Switch off IRE and call for service
assistance.

If the voltage is slightly higher but relatively constant and the
default values have been re-entered using the serial interface
on the CPHC16 -S p.c.b., then the synchronisation may need to
be re-adjusted. This can be easily confirmed by comparing the
two sinewaves for a possible phase difference.

Are the two waveforms phase-shifted?

yes:

The synchronisation must be re-adjusted using the serial
interface of the CPHC16 -S pcb and the PSRS232 and a
portable computer.

2 Initial Start-Up