5 remote panel, 2 installation – Powerware Uninterruptible Power Supply SOLA 4000 User Manual

Page 89

Advertising
background image

JUE 401267

89

SOLA 4000 - Operating Panel

5

REMOTE PANEL

5.1 General

The Remote Panel is used for remote monitoring of SOLA 4000
systems for distances of up to 400m. It is connected by cable via a
RS485 interface. It can be installed in a control room and provides
the same user interface as the local operating panel.

Only the E.P.O. function is not implemented.

5.2 Installation

The Remote Panel is connected to the UPS by a shielded cable
4x0.5mm of max. 400m length with 9-pole sub-D connectors.

9-pole male sub-D connector, fits
in the remote panel

9-pole male sub-D connector,
fits in the UPS local panel

The Remote Panel is mounted in a box (270x160x80mm).

The Remote Panel is supplied by an external power supply 220/
230/240 V

ac

, 50 Hz (which must be connected to the output of the

UPS).

The connection between the UPS and the Remote Panel is pro-
vided by a Keyboard 5-Wire Jack.

For the Remote Panel housing the same colour is used as for the
SOLA 4000 cabinets.

5 Remote Panel

Advertising