Troubleshooting

What This Chapter Contains

This chapter describes the diagnostics provided by the LED diagnostic
indicators on the 1771-SDN module’s front panel.

Module Status Indicator

The bicolor (green/red) Module Status LED indicates whether the
1771-SDN module has power and is functioning properly.

For information about the

See page

Module Status Indicator

7-1

Network Status Indicator

7-2

Node/Error Code Indicator

7-2

Module Status Indicator

If the indicator
is

Then

Take this action

Off

There is no power applied to the
module.

Verify power connections and
apply power.

Green

The module is operating normally.

No action required.

Flashing Green

The module is not configured.

Configure the module.

Flashing Red

There is an invalid configuration.

Verify DIP switch settings. Check
configuration setup.

Red

The module has an unrecoverable
fault.

Replace the module.