Rsnetworx software as a configuration tool, Rsnetworx software as a configuration tool -9 – Rockwell SoniCrafter DEVICENET 1771-SDN User Manual

Page 25

Advertising
background image

Publication 1771-6.5.132 - June 2000

Before You Begin 1-9

exactly where in each device’s total data to find the desired data

the size of the input data/output data

exactly where to map the input or output data for your
processor to read or write

RSNetWorx Software as a
Configuration Tool

RSNetWorx for DeviceNet software is used to configure the 1771-SDN
module’s data tables. This software tool connects to the 1771-SDN
module over the DeviceNet network via a PC RS–232 interface
(1770–KFD module), or PC Card (1784-PCD, -PCID, or PCIDS).

User
Configured
Tables

Data In This Table

RSNetWorx Configuration
Screen

SCT

basic operation

module parameters

interscan delay

background poll ratio

1771-SDN Module Configuration

SLT

device-specific
identification data

Scanlist Editor (SLE)

data transfer method

transmit/receive data size

Edit Device I/O Parameters

input and output data
source and destination
locations

These values can be configured
automatically through the
AutoMap function or manually
through the Data Table Map.

Interscan delay is the time between
I/O scans (polled and strobed). It is
the time the 1771-SDN module will
wait between the last poll message
request and the start of the next scan
cycle.

Background poll ratio sets the
frequency of poll messages to a
device in relation to the number of
I/O scans. For example, if the ratio
is set at 10, that device will be
polled once every 10 scans.

TIP

RSNetWorx for DeviceNet software can also
communicate with the 1771-SDN module via a
ControlNet, Ethernet, or Data Highway Plus network.
See chapter 5.

Advertising