Rockwell SoniCrafter DEVICENET 1771-SDN User Manual

Page 34

Advertising
background image

Publication 1771-6.5.132 - June 2000

2-6 Planning Your Configuration and Data Mapping Your Devices

Mapping RediSTATION Output Data for a Block Transfer Write

The RediSTATION operator interface’s output byte is mapped to the
1771-SDN module’s block transfer write data table. Within the output
byte is bit 0 for the indicator light. The PLC-5’s output data file is
transferred by the processor application to turn the light on or off. In
this example, we use N10 for the output data file.

1

start/stop station node address 7

L = bit for the station

indicator light

2

The PLC-5 processor’s output
data file containing the indicator
light bit for the RediSTATION is
transferred via a BTW to the
1771-SDN Scanner’s BTW data
table.

What’s Happening?

The BTW data table is then sent
to the RediSTATION via a polled
message from which the
RediSTATION receives its
indicator light bit.

= unused bits

2

RediSTATION Output

1 byte

L

1

Example: The RediSTATION’s indicator light (L) is taken
from N10:1/0 in the PLC-5 processor’s output data file.

1

This mapping is based upon the example in chapter 4.
The actual mapping for your system may be different.

= bits reserved for module

status word

Word 0

Word 1

Word 2

Word 3

Word 4

Word 61

1771-SDN Scanner Block Transfer Write Data Table

L

reserved for module status word

N10:0

0000 0000 0000 0000

N10:1

0000 0000 0000 000L

N10:2

0000 0000 0000 0000

N10:3

0000 0000 0000 0000

N10:5

0000 0000 0000 0000

N10:4

0000 0000 0000 0000

PLC-5 Processor

Output Data File

1

N10:61

0000 0000 0000 0000

Note: This example uses
1-slot addressing.

Advertising