Publication 1771-6.5.132 - June 2000

Hardware Setup 3-11

Installing the RediSTATION
Operator Interface

Begin installing the RediSTATION by removing the six screws
fastening the cover and setting the DIP switches inside as follows:

See Chapter 2 of the RediSTATION Operator Interface User Manual,
publication 2705-804, for complete information about setting the DIP
switches to configure the node address, data rate, output flash rate,
and output fault state.

Refer to the following illustration as you connect the RediSTATION to
the network.

Set this position

To this value:

1
2
3
4
5
6

1

On

1

On

1

On

(node

0

Off

address

1

)

0

Off

0

Off

7
8

0

Off

(data

1

On

rate

2

)

9

10

0

Off

0

Off

1

The DeviceNet address is 000111 (node 7).

2

The data rate is 10 (500k bps).

The output fault rate is 0 (outputs turned off).
The output flash rate is 0 (outputs tuned off).

More

DeviceNet Cable

The DeviceNet cable connects directly
to the mini connector on the top of the
RediSTATION enclosure or through the
conduit opening (open style).

TIP

You do not need to
disconnect incoming
power from the
DeviceNet network
before connecting
the RediSTATION.