Communicating with Your
PLC-5 Processor

Your processor communicates with the 1771-SDN scanner module via
block transfer reads, block transfer writes, and DIO transfers.
Input data, gathered from the network’s devices, is organized within
the 1771-SDN and made available for the processor to “read”.

The 1771-SDN module does not send data to your processor.
Data transferred between the module and the processor must be
initiated by the processor.

Output data is sent, or “written”, to the

scanner by your processor. This data is organized in the 1771-SDN
module, which in turn passes the data on to your scanned devices via
strobe, poll, change of state, or cyclic messages.

A block transfer read (BTR) is
a block transfer of data from
the 1771-SDN module to the
PLC processor. The processor
is

reading the data collected

by the 1771-SDN module
(i.e., DeviceNet input data).

A block transfer write (BTW)
is a block transfer of data
from the PLC processor to
the 1771-SDN module. The
processor is

writing the data

to the 1771-SDN’s memory
(i.e., DeviceNet output data).

PLC-5 Processor

1771-SDN Scanner

B

A1

C

D

A2

E

E

X

Y

Y

Z

Y

Y

C

D

A2

X

Z

Y

Y

Y

Y

Discrete Input Image

Block Transfer Data File

A1

B

E

E

Internal Input
Data Storage

I/O Map

Input from
the devices

Discrete Output Image

Block Transfer Data File

Internal
Output Data

I/O Map

Discrete I/O
Transfer

Block
Transfer
Write

Discrete I/O
Transfer

Block
Transfer
Read

Output to
the devices