3.3 Clearance Data -U Tube

NOTE:

1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.

2. Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream

from the burner.

3. All measurements are in millimeters.
4. Add 60 mm clearance to uncovered U-tube.

FIGURE 11: U-TUBE, HORIZONTAL MOUNT

Mo

del

BH15UT

BH20UT

BH25UT/EF

BH30UT/EF

BH35UT/EF

BH40UT/EF

BH45UT/EF

BH50UT/EF

A

150

150

150

150

150

150

200

200

B

890

970

970

1020

1170

1220

1270

1380

C

1580

1730

1730

1910

1980

2050

2110

2210

D

760

940

940

1000

1090

1150

1200

1300

A

C

D

B

FIGURE 12: U-TUBE, ONE SIDE REFLECTOR

Model

BH15UT

BH20UT

BH25UT/EF

BH30UT/EF

BH35UT/EF

BH40UT/EF

BH45UT/EF

BH50UT/EF

A

150

150

150

150

150

150

200

200

B

230

230

230

230

230

230

230

230

C

1580

1760

1760

1930

2090

2130

2160

2240

D

1200

1380

1380

1500

1660

1710

1760

1860

A

C

D

B

FIGURE 13: U-TUBE, TWO SIDE REFLECTORS

Model

BH

1

5

U

T

BH

2

0

U

T

BH

2

5

U

T

/EF

BH

3

0

U

T

/EF

BH

3

5

U

T

/EF

BH

4

0

U

T

/EF

BH

4

5

U

T

/EF

BH

5

0

U

T

/EF

A

150

150

150

150

150

150

200

200

B

590

640

640

690

820

860

890

1020

C

1660

1810

1810

1960

2110

2160

2210

2320

D

590

640

640

690

820

860

890

1020

A

C

D

B

FIGURE 14: U-TUBE, FULL 45° MOUNT

Model

BH

1

5

U

T

BH

2

0

U

T

BH

2

5

U

T

/EF

BH

3

0

U

T

/EF

BH

3

5

U

T

/EF

BH

4

0

U

T

/EF

BH

4

5

U

T

/EF

BH

5

0

U

T

/EF

A

200

200

200

200

200

200

200

200

B

200

200

200

200

200

200

200

200

C

1500

1650

1650

1860

1960

2040

2110

2160

D

1070

1170

1170

1320

1550

1620

1680

1780

B