the attention of the user or purchaser; instruct them in the
safe operation of the heater(s). Advise the user that if the
system is unflued, any reduction in the natural ventilation
of the building may require a flue to be fitted, or additional
ventilation grilles will be required.

14.6 ECA Approved Systems (Multiburner only)

On ECA approved systems, it must be verified that the
requirement of 91% net combustion efficiency is met.
Measurements of temperature and CO

2

concentration in

the exhaust gasses have to be done. The net combustion
efficiency calculates as follows;

100 - [ (t

E

- t

R

) (A/CO

2m

- B) ] = net combustion efficiency

t

E

- Exhaust Temperature °C

t

R

- Room Temperature °C

A

- G20 = 0.37, G31 = 0.42

B

- G20 = 0.009, G31 = 0.008

CO

2m

- Measured CO

2

Concentration %